ALSTOM

ALSTOM 232 590.043149 Unit Processor A

ALSTOM 232 590.043149 Unit Processor A

Ethernet switch

The Ethernet switch shall meet the following standards:

• EMC immunity for industry EN 50082-2 or EN 61000-6-2

Alstom Power Service has successfully used the switches from HMS

Industrial Networks, Sweden and different types of switches from

Hirschman Electronics.

1.4. Ethernet hub

Ethernet hub should not be used in a new installation, because it will

decrease the performance of the network. With a hub in the network it is also

more difficult to calculate the allowed cable lengths.

1.5. Connection to controller

The Ethernet board connection on the controller is of the

following type:

• RJ45 10/100M/bit auto negotiation

1.6. Cables

Cat 5E FTP cables with RJ45 connectors are recommended for the Ethernet

network.

1.7. Ethernet ports and protocols

The following Ethernet ports are used:

• Port 20. 21 for FTP

• Port 80 for HTTP

• Port 502 for Modbus/TCP data

• Port 3 250 for PC-MTU – IP config

• Port 49 200. 49 201 for the master functionality and PC-MTU.

1.8. Ethernet routers

Routers should not be installed in the EPIC III Ethernet network. The PC

MTU and master functionality will not function properly through it.

Network node address lists A list of all nodes with name and addresses

made by ALSTOM Power Service.

ALSTOM PIB903
ALSTOM POS1846 TRVC062333000 CP00000310
ALSTOM SDK-C0147 12004-101-00 SBS04M17C
ALSTOM SDK-C0148 12003-101-01 SBS05M09B
ALSTOM SDK-C0167-1 12004-08-01 SBS07M076B
ALSTOM STO1726KO1
ALSTOM TRVC062105000 TRVC070938000 TRVC070938005.A
ALSTOM UT150-1
ALSTOM V0701596-001102
ALSTOM V4555724-0100
ALSTOM V4561983-0100
ALSTOM VCS232 590.043158

Node

PC-MTU

ProMo

ROM

Router

RTU

Subnet

SCR

TCP/IP

TP

T/R

T/R On/Off

Web browser

Webserver

A node (unit) is a single addressable entity on a

TCP/IP network.

Software used to set-up and monitor an

installation of several EPICs.

A colour graphic software package for process

control.

Read Only Memory.

An active network component that connects

one network to another network.

Remote Terminal Unit gives operators an alpha

numerical and graphical interface to ESP

parameters.

The IP address is divided into three parts to

seperate them from each other a Subnet mask is

used.

Silicon Controlled Rectifier.

Transmission Control Protocol/Internet

Protocol. TCP/IP is a collection of

protocols that control the way data travels from

one node to another across a network.

Twisted Pair (type of cable used e.g. in Ether

net).

Transformer/rectifier.

High voltage On/Off.

A software used to browse or show web (Inter

net) pages e.g. Microsoft Internet Explorer.

A computer (software and hardware) used to

supply client workstations with Web pages.