ALSTOM

ALSTOM 20X4284 Driving Board

Removal of the Drive Data Manager™ (Keypad)

NOTE: To allow the drive to make the necessary safety checks, this removal procedure should always be

followed.  A trip may result if this procedure is not followed.

The drive checks if Keypad removal is allowed as the Keypad may have Start/Stop control, or the Keypad

Speed Reference may be active.

To remove the Keypad, continue as shown in Table 2-1.

Do What? How?

1 Ensure the keypad is neither in control of

the Start/Stop nor the keypad Speed

Reference is active

AT DEFAULT:

Simply close DIGIN4. this will select

Remote.

ELSE:

Gain the necessary authorisation

before continuing.

a)  Make P34.16 = 1. to set CF116 ON, this

removes the Start/Stop control from the keypad.

b)  If a machine bridge, the keypad must

not be either the active reference source or the

backup reference source. The reference sources

are held in P5.01 to P5.05 and are made active

by CF4 to CF7 (P5.07 to P5.10) respectively.

2 Access the keypad removal screen

Press the “esc” key repeatedly.

3 Select “REMOVAL CHECK” Press the “1” key on the keypad

The converter checks to see if the keypad is

allowed to be removed. As well as the above

control and reference checks, P35.01 (Allow

keypad Removal) is also checked.

4 Remove keypad if the screen allows:

A message may be flashed disallowing removal

because the keypad is either still in control, still

has active/backup reference

(see step 1 above) or if it is simply disallowed (see

step 3 above).

Table 2-1. – How to Remove the Drive Data ManagerTM (keypad)

2.3 RECALLING A PARAMETER SET FROM A DRIVE DATA MANAGER™

The  MV3000e MicroCubicle™ and the  MV3000e DELTA AC Drives incorporate a feature to enable the

transfer of parameters from one drive to another via the  Drive Data Manager™ (where the Parameter Set

can be saved).  This feature is invoked via Parameter P99.16 – Backup Parameter – see Section 6.57.11.

Recalling a Parameter Set from one drive to another is a very powerful and useful feature.  However, care

must be taken to ensure that an incorrect Parameter Set in the target drive does not result from copying

the Parameter Set from an inappropriately configured drive, particularly from a drive of different rating from

the source drive.  It is therefore recommended that reference be made to the additional guidance in ‘Notes

for Recalling a Parameter Set from the Drive Data Manager™ (Keypad)’ in Section 6.57.11