Foxboro P0950CA Centralized and Distributed Control Module
Discrete Inputs
Various termination assemblies are available to support the interfacing of field signals
to the low level FBM input circuits. Active termination assemblies support input signal
conditioning for the FBM as well as channel isolation.
Be aware that for configurations which use main and expansion TAs, the I/O signal
conditioning circuits are designed to emulate the 100 Series FBM I/O subsystem. This
provides for functional I/O equivalence during upgrades from 100 Series to 200 Series
hardware.
The signal conditioning circuits are located on daughter boards that are mounted
under the component covers of the termination assemblies. To condition signals,
these termination assemblies provide optical isolation, current limiting, voltage
attenuation and optional terminal blocks to connect externally supplied excitation
voltage.
LowVoltage Discrete Inputs
The low voltage inputs (less than 60 VDC) use passive termination assemblies. Inputs
are voltage monitor or contact sense types. Voltage monitor inputs require an external
field voltage source. Contact sense inputs use the FBM auxiliary +24 VDCpower
supply to wet field contacts.
Aload may be required for proper operation of the input channels.
High Voltage Discrete Inputs
The high voltage input circuits support 125 VDC, 120 VAC, or 240 VAC. Voltage
monitor inputs require a field voltage source.
Someversions of the termination assembly have a pair of external excitation voltage
terminals, which distribute customer-supplied wetting voltage to all input channels on
the assembly. These terminals allow the field power to be daisy chained between
terminal assemblies