Foxboro PSS41H-2G62 G62and G72Tricon System and Termination Enclosures
Field Termination Assemblies
Termination Assemblies (TAs) are installed on the DIN rails mounted at the sides of
the FBM baseplates. The Universal I/O modules are connected to the TAs with pre
installed system cables.
The TAs are supplied with redundant 24 V DC, protected by fuses that are monitored
by the Fuse Monitoring Unit (FMU).
The enclosure is shipped with TAs fitted with passive feed-through signal conditioners
which you can replace with the signal conditioners listed in the section Termination
Assemblies and Signal Conditioners, page 8.
Power Distribution Architecture
The enclosure provides a redundant 24 V power system using two FPS480-24 power
supplies fed by independent sources. Power wiring is routed through the bottom of the
enclosure. The input power connects to the primary and secondary entry terminal
blocks for main and backup power.
Electrical fuses are monitored by the Fuse Monitoring Unit (FMU) and an open fuse
indication from the FMU is wired into the Enclosure Monitoring Unit (EMU) through the
Alarm Distribution Assembly.
Grounding
All enclosure structural elements are integrally grounded by the enclosure design to
meet the appropriate industry regulations and standards. The enclosure is equipped
with two instrument earth bars. It also has a protective connection point at the outside
bottom of the enclosure for customer grounding purposes. Field wiring shields can be
terminated either to the Terminal Assemblies or to the instrument ground bus bar.
Spare signal wires and shields can be terminated either to the Terminal Assemblies or
to the instrument ground bus bar.
The G61enclosure is available as a vented or sealed enclosure. It can be configured
with:
| HITACHI | LPD350A |
| HITACHI | LPF240A |
| HITACHI | LPF240F |
| HITACHI | LPP100A |
| HITACHI | LPT020A |
| HITACHI | LPU100A |
| HITACHI | LPU100H |
| HITACHI | LUD060A |
| HITACHI | LUD700A |
| HITACHI | LYA010A |
| HITACHI | LYA100A |
| HITACHI | LYA210A |
| HITACHI | LYA220A |
| HITACHI | LYD105A |
• Uptosevenvertical DIN rails for mounting of Triconex termination devices and
additional customer-supplied terminal blocks for marshalling
• Redundantpowersupplies (480 W or 960 W 24 VDCpower supplies) for field
power
The G61vented enclosure is a free-standing, floor mounted unit with an IP43/55
rating for location in mild (ordinary) environmental areas.
The G61sealed enclosure is a free-standing, floor mounted unit, with options for
either an IP55 or IP66 rating for location in harsh environments.
Sealed enclosures with an IP66 rating provide a higher level of protection from
airborne contamination.
NOTE: In regions that require EMC compliance, you must order the EMC
compliance option if the Triconex termination devices for Tricon modules SMM or
SRXMwill be installed in this enclosure. Without these termination devices, the
enclosure already fulfills the requirements for EMC compliance.
An optional door intrusion monitoring switch is available for each door on this
enclosure. Each switch is prewired to a set of alarm status terminal blocks.
The G61enclosure can be installed bayed or adjoined to other Triconex enclosures to
maximize the use of floor space and ease of cabling. The enclosures can be bayed
together using third-party kits.
This enclosure and its configurations have been tested and qualified by Foxboro for
use with the Tricon equipment.