Foxboro P0916PH P0916JS Industrial Control Module
OVERVIEW
The Intrinsically Safe I/O Subsystem provides
integration between the Pepperl+Fuchs (P+F)
modular intrinsically safe remote I/O systems and the
I/A Series system. The Intrinsically Safe
Communications Module (ISCM) communicates
between the two systems, as it enables I/A Series
control processors to view supported P+F intrinsically
safe I/O modules as equivalent 200 Series Fieldbus
Modules (FBMs) over the I/A Series 2 Mbps HDLC
Fieldbus. This allows the I/O modules to be
monitored with standard I/A Series blocks and
standard I/A Series or InFusion system/control
configurator applications such as InFusion
Engineering Environment and ICC.
This subsystem supports both the P+F intrinsically
safe I/O modules and their associated base,
extension or redundancy units for Zone 2. Div. 2 or
Zone 22 (LB-style(1)) environments or
Zone 1 or Zone 21 (FB-style(2)) environments.
Optionally redundant ISCMs are mounted directly on
the appropriate P+F unit along with the I/O modules
and power supplies, as shown in Figure 1 and
Figure 2. Only I/O modules can be mounted in the
extension units. Each I/O module can be plugged
into any desired slot on the base or extension unit.
ISCMs and power supplies are required to be
plugged into their own dedicated slots
Depending on the model type used, I/O modules can
occupy one or two slots in their unit.
ISCMs are installed as single or redundant. In
redundant configurations, both ISCMs are always
active. In case of a module’s failure, the other
provides backup coverage until the failed ISCM is
returned to service. An ISCM for Zone 2 applications
may support up to 46 LB-style I/O modules, while an
ISCM for Zone 1 applications may support up to 48
FB-style I/O modules.
| GE | SBI-PDP-32 |
| GE | SD-108542 |
| GE | SD-98762 |
| GE | SLN042 IC086SLN042-A |
| GE | SLN080 IC086SLN080-A |
| GE | SM128V |
| GE | SR465-P5-HI-A20 |
The following 200 Series FBM features are
not supported on the intrinsically safe I/O
modules: Sequence of Events (SOE), TDR,
time synchronization, ladder logic, and the
EVENT, MDACT and DPIDA blocks.
NOTE
The limit of sixteen ISCMs per subsystem
represents the theoretical maximum if the
base, extension or redundancy units are not
fully fitted with modules. Sixteen base units
with sixteen extension units will connect a
total of 16 x 46 I/O modules (736). The
controller can handle up to 204. If dual-width
modules are used, then the subsystem will
have 16 x 23 dual-width I/O modules (368)
which is outside the scope of the
subsystem. In typical scenarios, eight units
can be connected to one FCP270.