Triconex Main Processor Baseplate Kit 2101
You can identify alarm and fault conditions in the following ways:
• By examining the indicators on the front panel of each module and consulting this chapter.
• By using the Diagnostic Panel in the TriStation application.
For more information, see the TriStation 1131 Developer’s Guide.
Fault and Alarm Indicators
Fault indicators identify potentially serious problems with a module. Alarm
conditions identify abnormal field conditions such as loss of power and loss of communication.
If a fault or alarm indicator is on, you should consult the appropriate section of this
chapter and take appropriate action. This action may include replacing a faulty
module or repairing a faulty circuit or device.
Triconex Communication Interface Module (TCMI)
The TCMI is a standard Honeywell product that provides interface between the Fault Tolerant Ethernet (FTE)
based Enhanced Universal Control Network (EUCN) and Triconex TRICON Safety Manager System.
The TCMI is a redundant device capable of:
• Bi-directional communication with Triconex systems 10.3 and above.
• Execution of data mapping of TRICON memory tables to EUCN format
• Data conversion to EUCN data types (Tag. Parameter), engineering unit and EUCN communication functions.
• Execution of read and write function to TRICON memory tables
• Definition of signal alarm conditioning and messaging on the EUCN for alarm handling, annunciation
and diagnostic status reporting
• Direct peer-to-peer communication with other EUCN connected devices as Enhanced HighPerformance Process Managers (EHPM), Enhanced Logic Managers (ELMM) or Honeywell Safety
Manager (SM)
16-Point Commoned Digital Output Term Panels
This section describes 16-point commoned digital output term panels, which are available in AC
versions or DC versions, and with fuses or without fuses. Model numbers of these term panels
are:
• 9661-610 (115 VAC, commoned, 16 pts.)
• 9661-910 (120 VDC, commoned, 16 pts.)
• 9662-610 (24 VDC, commoned, 16 pts.)
• 9662-810 (24 VDC, commoned, 16 pts.)
• 9663-610 (115 VAC, commoned, 16 pts.)
• 9664-810 (120 VDC, commoned, 16 pts.)
• 9667-810 (48 VDC, commoned, 16 pts.)
This figure represents a typical 16-point commoned DC digital output termination panel
Typical 16-Point Commoned DC DO Term Panel with Fuses
This figure represents a typical 16-point commoned digital output panel without fuses
• Communication with operators, engineers, and maintenance personnel at the Universal Stations, EST & ESVT via ENIM.
• Support of higher level strategies through communication with Application Modules and host
computers on the Local Control Network via ENIM.
• Database restoration of TCMI Module from the History Module via ENIM.
• Available in two hardware mounting form, front and rear cabinet access mounting (MC-ZTCMIR or
MC-TCMIR1), Front only cabinet access mounting (MC-ZTCMI2 or MC-TCMIR2)
Model 9764-310 RTD/TC/AI Termination Panel
The Model 9764-310 RTD/TC/AI Termination Panel with industry-standard
signal-conditioning modules may be cabled to the Model 2352 Analog Input
External Termination Panel Baseplate. The RTD/TC/AI Termination Panel
supports 16 points and each Analog Input Module can support up to two External
Termination Panel. The input-signal conditioners are manufactured by Analog Devices™.
The Model 9764-310 panel comes with a:
• 10-foot cable
• Mounting plate
The Model 9764-310 panel has a barrier strip with four compression screw
terminals for connecting an AI Module to 16 analog inputs. The panel accepts
power (+24 volts DC) from the AI Baseplate or from direct connection to the panel.