DEIF

DEIF MVR-G215 Generator Protection

MVR-G215

Generator Protection

The MVR-G215 generator protection relay is a compact solution for applications that require voltage and current based protection of small and medium sized generators.

The MVR-G215 is a compact generator protection relay for small and medium sized generators. It comes with voltage and current based protection. Communication interfaces and I/Os can be extended with the 3 available extension slots as required by the individual application.

5x Current input (configurable 0.2…10A)

4x Voltage input (1.00…480.00V (RMS)

3x Digital input

5x Output relay (4NO, 1CO)

1x IRF output (1CO)

2x Remote com port (1 x RJ45 Ethernet and 1 x RS-485)

– IEC 61850 Ed1. Modbus TCP/RTU, IEC 60870-5-104/103/101. DNP 3.0. SPA protocols

– 3 extension slots for additional hardware options

– Event recorder (up to 15 000 events)

– Disturbance recorder (up to 100 disturbance records

Available Extension Cards:

– 8x digital inputs (programmable threshold voltage)

– 5x output relays

– Arc-Flash Protection – 4x sensor channels, 2x HSO1. 1x BI *)

– 8x RTD input

– 2x RJ45 100Mb Ethernet & IRIG-B *)

– 2x ST 100Mb Ethernet & IRIG-B *)

– 4x mA outputs – 1 x mA input

– 2x LC 100MB Ethernet (HSR, PRP redundant protocols)

– 2x RJ45 100MB Ethernet (HSR, PRP redundant protocols) *)

– RS-232 – Serial Fiber

Features

Protection Functions:

(Sensitive) Earth fault protection stages INST, DT or IDMT (ANSI 50N/51N(S))

100% Stator Earth fault protection (ANSI 64F3)

Auto-reclose (ANSI 79)

Breaker failure protection (ANSI 50BF)

Cable-end differential protection (ANSI 87)

Current transformer supervision (ANSI 60L)

Current unbalance/broken conductor protection stages INST, DT or IDMT (ANSI 46 /R/L)

Directional (sensitive) residual over-current protection stages DT or IDMT (ANSI 67N)

Directional three-phase over-current protection stages DT or IDMT (ANSI 67)

Frequency protection stages (ANSI 81O/U)

Fuse failure (ANSI 60)

Harmonic over-current protection/inrush blocking stages INST, DT or IDMT (ANSI 50H/51H/68)

Loss of field (ANSI 40)

Machine thermal overload protection (ANSI 49M)

Over-excitation protection (ANSI 24)

Overvoltage protection INST, DT or IDMT (ANSI 59)

Positive/negative sequence under-/over-voltage protection INST, DT or IDMT (ANSI 27P/47/59P)

Power factor (ANSI 55)

Programmable stage (ANSI 99)

Rate of Change of Frequency ROCOF (ANSI 81R)

Residual voltage protection INST, DT or IDMT (ANSI 59N)

Restricted low-impedance earth fault protection (ANSI 87N)

Reverse-/under-/over-power protection INDT, DT or IDMT (ANSI 32)

Synchrocheck (ANSI 25)

Three-phase over-current protection INST, DT or IDMT (ANSI 50/51)

Under-impedance protection (ANSI 21)

Under-voltage protection INST, DT or IDMT (ANSI 27)

Vector jump/surge (ANSI 78)

Voltage controlled/dependent over-current protection (ANSI 51V)

Voltage memory