DEIF MVR-F201 Basic Feeder Protection
MVR-F201
Basic Feeder Protection
The MVR-201 overcurrent and earth fault relay offers reliable protection at the best cost-performance ratio.
The MVR-F201 overcurrent and earth fault protection relay is a compact solution for any application that requires non-directional overcurrent and earth fault protection at the best cost-performance ratio.
– 5-phase current measuring
– 5 x Current input (configurable 0.2…10A)
– 3x Digital input
– 5x Output relay (4NO, 1CO)
– 1x IRF output (1CO)
– 2x Remote com port (1 x RJ45 Ethernet and 1 x RS-485)
– Modbus TCP/RTU, IEC 60870-5-104/103/101. DNP 3.0. SPA protocols
– DT, IEC or ANSI time/overcurrent curves with settable release delays
– Event recorder (up to 15 000 events)
– Disturbance recorder (up to 100 disturbance records)
Marine approvals
– DNV/GL
– Lloyds Registeres LR
– Bureau Vertias BR
– ABS (USA)
– CCS (China)
– CNK (Japan)
– IEC (Israel)
– KR (Korea)
– UKCA (UK)
– RINA (Italy)
Features
Protection Functions:
Three-phase over-current protection INST, DT or IDMT (ANSI 50/51)
(Sensitive) Earth fault protection stages INST, DT or IDMT (ANSI 50N/51N(S))
Breaker failure protection (ANSI 50BF)
Cold-load pick-up block (ANSI 68)
Current transformer supervision (ANSI 60L)
Current unbalance/broken conductor protection stages INST, DT or IDMT (ANSI 46 /R/L)
Harmonic over-current protection/inrush blocking stages INST, DT or IDMT (ANSI 50H/51H/68)
Switch onto fault logic (SOTF)
Thermal overload protection (line) (ANSI 49L)