SAUTER

SAUTER Linear valve actuator AXT/AXS series AXT211

Linear valve actuator AXT/AXS series    AXT201

AXT 201. 211: Thermal actuator for unit valves with stroke

indicator

How energy efficiency is improved

Reliable actuation in efficient control systems

Features

• Fitted to the valve using no force thanks to the Low-Force-Locking (LFL) connector

• Fitted onto valve with M30 x 1.5 thread with automatic adjustment of closing dimension

• Pushing force max. 125 N

•With 230 V or 24 V thermal expansion element

• Large visible position indicator

• NC “normally closed” and NO “normally open” models (with and without auxiliary contacts)

•Model with manual adjustment

• Silent and maintenance-free

•Modular electrical plug connection (various functions, cable lengths and types)

• Including bayonet nut made of plastic M30 × 1.5

• Suitable for retrofitting existing installations without an adapter

• Fitting in any position, including upside down

Technical data

Power supply

Power supply 24 V~ ±20%, 50…60 Hz

Power supply 24 V= ±20%

Power supply 230 V~ ±15%, 50…60 Hz

Power consumption during operation 2.5 W (230 V~), 3 W (24 =/~)

Starting power 24 V~/= 5 W/5 VA

Starting power 230 V~ 40 W/40 VA

Start-up current 24 V~ 220 mA

Start-up current 230 V~ 150 mA

Parameters

Stroke Max. 4.5 mm

Ambient conditions

Operating temperature at valve 100 °C max.

Storage and transport temperature −25…70 °C

Admissible ambient temperature 0…50 °C

Admissible ambient humidity < 85% rh, no condensation

Construction

Housing Pure white (RAL 9010) or jet black

(RAL 9005), high-gloss surface (FV-0

as per EN 60707 and V-0 as per

UL94)

Housing material Fire-retardant plastic

Power cable Standard length 0.8 m (AXT201), 1 m

(AXT211. H03…), PVC, 2 x 0.50 mm²,

white/black

Standards and directives

Type of protection IP54 (EN 60529)

Protection class 24 V III (EN 60730-1)

Protection class 230 V II (EN 60730-1)

CE conformity according to Low-Voltage Directive 2014/35/EU EN 60730-1. EN 60730-2-14

EN 60335-1

RoHS Directive 2011/65/EU EN 50581

EMC Directive 2014/30/EU EN 61000-6-1. EN 61000-6-2

EN 61000-6-3. EN 61000-6-4

Overview of types

Type Features

AXT201F110 White version 230 V, NC, neutral, incl. raised M30 × 1.5 bayonet nut, cable 0.8 m

AXT201F112 White version 24 V, NC, incl. raised M30 × 1.5 bayonet nut, cable 1 m

AXT211F100 White version 230 V, NC, without cable, pack of one

AXT211F100B Black version 230 V, NC, without cable, pack of one

AXT211F102 White version 24 V, NC, without cable, pack of one

AXT211F102B Black version 24 V, NC, without cable, pack of one

AXT211F110 White version 230 V, NC, cable 1 m

AXT211F110B Black version 230 V, NC, cable 1 m

AXT211F110M White version 230 V, NC, with manual adjustment, cable 1 m

AXT211F112 White version 24 V, NC, cable 1 m

AXT211F112B Black version 24 V, NC, cable 1 m

AXT211F112M White version 24 V, NC, with manual adjustment, cable 1 m

AXT211F190 White version 230 V, NC, packing unit 50 pcs, without cable

AXT211F192 White version 24 V, NC, packing unit 50 pcs, without cable

AXT211F200 White version 230 V, NO, without cable, pack of one

AXT211F202 White version 24 V, NO, without cable, pack of one

AXT211F210 White version 230 V, NO, cable 1 m

AXT211F212 White version 24 V, NO, cable 1 m

AXT211HF110 White version 230 V, NC, with auxiliary contacts, cable 1 m

AXT211HF210 White version 230 V, NO, with auxiliary contacts, cable 1 m

AXT211HF112 White version 24 V, NC, with auxiliary contacts, cable 1 m

AXT211HF212 White version 24 V, NO, with auxiliary contacts, cable 1 m

Rolls-Royce R02TCN-EOL3-00
ABB 3BHE014023R0101 UFC789AE101
GE MIVII1000E00HI00
GE MIFIIPA55E20HI00
GE IS220PAOCH1BE
GE Is220Ydias1A
GE Is220Pd0Ah1B
GE IS220YDOAS1A
ABB DSAO120 5FSE707630-71
Rolls-Royce 98H010A00001
moog G771K202
GE IS420UCSBH4A Rev.I
GE IS420UCSBH1A Rev.H
ABB EL3020 3.345558.2 0241398794/0300
Magnos 206 O2 98-100%
ABB EL3020 3.346806.2 0241398794/1500
Caldos 27 Ar 0-100%
ABB AX410/50001
Foxboro FBM217
Foxboro FBM201 P0914SQ
Foxboro FBM237 P0914XS

​