SAUTER AKM115F122 Rotating actuator AKM 105/115 series
SAUTER AKM115F122 Rotating actuator AKM 105/115 series
For operating 2- and 3-way ball valves VKR, VKRA, BKR, BKRA, VKAI, VKAA, BKLI, BKTI, BKTA, (AKM115) and 6-way ball valve B2KL
For controllers with a switching output (2-/3-point control)
Assembly with ball valves without the use of tools
Synchronous motor with electronic activation and cut-out
Maintenance-free gear unit
Gear unit can be disengaged in order to position the ball valve manually (using the lever)
Bracket and bayonet ring made of glass-fibre-reinforced plastic for fitting onto ball valve
Fitting vertically upright to horizontal, not suspended
Accessories
Type
0372459100
0372459102
0510420001
0510240011
0510480001
0510480002
Description
External switching, 230 V version for parallel operation with A*M 1*4 or drives with limit switch,
incl. junction box
External switching, 24 V version for parallel operation with A*M 1*4 or drives with limit switch,
incl. junction box
Adaptor required when temperature of the medium > 100 °C
Adaptor required when temperature of the medium < 5 °C
Auxiliary change-over contacts, single
Auxiliary change-over contacts, double
A Auxiliary change-over contacts: infinitely variable 0…100%, admissible load 5(2) A, 24…230 V
Description of operation
When voltage is applied to the cable, the control unit to be activated is moved to any desired position
by means of the carrier stem.
Direction of rotation for 3-point control (viewing the spindle of the ball valve from the actuator):
• The stem turns in the anti-clockwise direction, with the voltage on the brown cable, and the through
passage of the ball valve is opened.
• The stem turns in the clockwise direction, with the voltage on the black cable, and the through pas
sage of the ball valve is closed.
With 3-point control, the direction of rotation is changed by swapping the connections.
Direction of rotation for 2-point control (viewing the spindle of the ball valve from the actuator):
There is always voltage on the black cable.
• The stem turns in the anti-clockwise direction, with the voltage on the brown cable, and the ball
valve is opened.
• The stem turns in the clockwise direction, with no voltage on the brown cable, and the ball valve is
closed.
In the end positions (limit stop in actuator), or in the case of an overload, the magnetic coupling is
activated. The positioning signal is switched off by the electronic cut-out after 3 minutes or 60 sec
onds (F100).
The manual adjustment is performed by releasing the gear unit (slide switch beside the connection
cable) and simultaneously turning it with the lever. The actuator position can be determined by look
ing at the lever or the indicator knob on the top part of the actuator
Intended use
This product is only suitable for the purpose intended by the manufacturer, as described in the “De
scription of operation” section.
All related product regulations must also be adhered to. Changing or converting the product is not ad
missible.
Engineering and fitting notes
Condensate, dripping water, etc. must be prevented from entering the actuator along the carrier stem.
Hanging position (fitting upside down) is not admissible.
The actuator/ball valve is mounted by inserting and turning the bayonet ring until the limit stop without
any additional adjustment. No tools are required. The coupling of the spindle of the ball valve with the
carrier stem is performed automatically, either by moving the manual adjuster to an angle of rotation
of 100% or connecting the voltage to terminals MM/N and 01. For dismantling, the bayonet ring is
simply opened and the actuator removed. The device is delivered ex works in the middle position.
The concept of a synchronous motor with magnetic coupling is performed by electrically connecting
multiple rotary actuators of type AKM in parallel (only with accessory 0372459 10 . ).
If a potentiometer is required, the accessory of the AVM 105. 115 can be used – the direction of oper
ation on the type plate is inverted. The maximum accessory equipment for an actuator is 1 auxiliary
change-over contact or 1 potentiometer.
The auxiliary change-over contact accessory is screwed onto the top cover of the actuator. To be able
to make the mechanical connection, you first have to remove the indicator knob. A new indicator can
be seen on the cover of the accessory.
Note! The housing must not be opened.
| Foxboro | P0916DE |
| ABB | 3BHE057901R0101 PCD235C101 |
| Triconex | 3704E |
| Triconex | 3504E |
| Triconex | 3504E |
| EMERSON | 1X00781H01L |
| EMERSON | PR6423 009-041+CON 041/913-030 |
| KONSGBERG | RCU500 |
| KONSGBERG | RMP400 |
| KONSGBERG | RDIOR400 |
| Cutler Hammer | 1775K PMPP1700 |
| MOORE INDUSTRIES | MDS/PRG/10-30DC/-MAO |
| ABB | DHH805-A |
| Wago | I/O-IPC 758-873 |
| CONVERTEAM | MVS3000-4001 |
| GE | MX150 |
| GE | IS215ACLEH1A |
| GE | IS200ERIOH1A |
| ABB | 1VCF752000 |
| YASKAWA | EUA615100 |