Attach the other end of the interface cable to the ELCO connector directly above the

corresponding I/O module on the Tricon backplane in the same manner as you

connected the cable to the termination panel, as described in step4.

6 Attach the wires from your field devices to the screw terminals on the termination panel.

See the Torque Specifications for Field Wiring Terminals section.

7 Perform a static check of the wiring.

8 If Tricon power was removed in step 1. restore power to the Tricon system.

9 Apply field power to the termination panel.

10 Verify that all I/O points are connected to the appropriate field devices and are

operating correctly.

Note To inspect input points and force output points, see the Planning and Installation

Guide for Tricon v9–v10 Systems.

11 Load and test the control program using TriStation.

If the program operates as intended, you are ready to enable the process equipment according

to the safety requirements for your environment.

If you need additional information on how to install external field termination panels, contact

the IPS Global Client Support (GCS) center.

Torque Specifications for Field Wiring Terminals

Tighten the screws on the field wiring and power terminals of the ETPs in the list below to this

torque:

4.425–5.310 lbf in (0.3688–0.4425 lbf ft) (0.5–0.6 Nm)

9551-110 9651-110 9664-110 9761-210 9787-110

9552-610 9652-610 9664-810 9761-410 9789-610

9553-610 9653-610 9667-110 9762-410 9790-610

9561-810 9661-610 9667-910 9762-210 9791-610

9561-110 9661-710 9667-610 9763-810 9792-610

9562-810 9661-110 9667-710 9765-210 9793-110

9563-810 9661-810 9667-810 9765-610 9794-110

9565-810 9661-510 9668-110 9766-210 9795-610

9565-710 9661-910 9750-410 9766-510 9853-610

9566-710 9662-110 9750-810 9771-210 9860-610

9566-810 9662-910 9750-210 9782-110 9861-610

9567-810 9662-610 9750-310 9783-110 9863-710

9570-610 9662-710 9753-110 9784-610

9571-610 9662-810 9760-410 9785-610

9572-610 9663-610 9760-210 9786-110

Tighten the screws on the field wiring and power terminals of the ETPs in the list below to this

torque:

12.0 lbf in (1.0 lbf ft) (1.36 Nm)

9670-110

9670-610

9671-610

9671-810

9672-810

9673-810

Removing or Replacing a Termination Panel

This procedure explains how to remove or replace a termination panel.

Procedure

1 Remove field power from the termination panel.

2 Detach all I/O points connected to the appropriate field wiring.

3 Detach the wires from your field devices to the screw terminals on the termination

panel.

4 Detach the interface cable from the ELCO connector on the termination panel.

• As you pull the connector on the cable, use your other hand to turn the thumbscrew

counter-clockwise. You may need to rock the connector slightly while pulling.

• Ensure that the mating surfaces of the ELCO connectors on the cable and the

termination panel do not have any bent pins or other damage.

5 Detach the other end of the interface cable from the ELCO connector on the Tricon

backplane in the same manner as you disconnected the cable from the termination panel,

as described in step 4