9662-1 TRICONEX terminal block
Specifications
This table describes specifications for 9563-910.
Table 26
Specifications for Term Panel 9563-910
Feature
Description
Panel type
Commoned, resistor protected
Points
16
Compatible Modules
This table describes digital input modules compatible with 9563-910.
Table 27
Modules Compatible with 9563-910
Module Part
Number
Points per
Module
Module Description
3503E
3505E
32
32
| FOXBORO | RH914TR |
| FOXBORO | P0926GU |
| YOKOGAWA | SCP451-11 |
| Honeywell | UT762AGA/Z |
| Honeywell | S0854485 |
| Honeywell | S0815344 |
| Honeywell | S0854962 |
| ABB | ACS880 ZCU-14 |
| GE | AT868-2-1-1 |
| Honeywell | FE-USI-0002 |
| MOOG | G771K202A |
| ABB | 07AC91 GJR5252300R0101 |
| Foxboro | RH101AB |
| Foxboro | 4000189-530 |
| ABB | DHH810-MFT |
| GE | MLJ1005B010F00C |
| ALSTOM | 029.359 325 |
| WOODWARD | E8250-502 |
| GE | SR489-P5-HI-A20 |
| ABB | 3BHL000391P0101 |
24 VAC/VDC, commoned in groups of 8. TMR with self-test
24 VDC, low-threshold, commoned in groups of 8. TMR with self-test
Field Wiring Diagrams
This figure illustrates how to connect a 32-point digital input module and a 9563-910 to the field.
Simplified Schematics
This is a simplified schematic of a typical 32-point commoned digital input module with self
test (1 of 32 module points shown)
32-Point Commoned Digital Input Term Panels
This section describes 32-point commoned digital input term panels, which are available with
fuses and blown fuse indicators or resistors for field device protection. Model numbers of these
term panels are:
• 9565-810 (48 VDC, commoned, 32 pts.) (fuse protection)
• 9566-710 (24 VDC, commoned, 32 pts.) (resistor protection)
• 9566-810 (24 VDC, commoned, 32 pts.) (resistor protection)
This figure represents a typical 32-point commoned digital input term panel that has fuses and
blown-fuse indicators for field device protection.
9565-810 (48 VDC, commoned, 32 pts.)
Termination panel 9565–810 is compatible with 24/48 volt DC digital input modules and has 32
input points and commoned power terminals (PWR+ and PWR–). Each input point is protected
by a fuse with a blown-fuse indicator. You should use term panel 9565-810 in 48 volt
applications.
The modules compatible with 9565–810 have 64 points, which means you must use two term
panels for each digital input module.
Each term panel comes with two sets of labels: 1-32 and 33-64. For information on how to apply
the labels, see Appendix F, Panel Labels.
Specifications
This table describes specifications for 9565–810.
Table 28
Specifications for Term Panel 9565–810
Feature
Description
Panel type
Commoned
Points
32
Leakage current per point
Maximum: 3.5 mA
Typical: 2.0 mA
Compatible Modules
This table describes digital input modules compatible with 9565–810.
Table 29
Modules Compatible with 9565–810
Module Part
Number
Points per
Module
Module Description
Fuse
3504E
64
24/48 VDC, commoned, high-density, DC-coupled,
TMR