Triconex

Triconex 3723X 32-Channel TMR Analog Input Module with HART

Triconex 3723X is a Triple Modular Redundant (TMR) Analog Input Module designed by Schneider Electric for high-integrity Safety Instrumented Systems (SIS). Used in Tricon CX chassis, it provides continuous 2-out-of-3 majority voting and pass-through support for HART-enabled smart field devices.

Product Overview

System Integrity: Operates on a TMR architecture to deliver SIL 3 compliant fault tolerance for Emergency Shutdown (ESD), Fire & Gas (F&G), and critical process interlocks.

HART Integration: Supports HART pass-through communication, enabling device configuration, diagnostics, and monitoring over existing analog wiring.

High Density: Features 32 single-ended input channels per module for efficient space utilization in process control cabinets.

Availability: Supports online hot-swapping to ensure zero downtime during maintenance.

Technical Specifications

Parameter Specification Details
Manufacturer Triconex / Schneider Electric
Model 3723X (AIH 3723X)
Module Type 32-Channel TMR Analog Input Module with HART
Compatible Chassis Tricon CX I/O Expansion Chassis
Architecture Triple Modular Redundancy (2-out-of-3 voting)
Input Signals 0 to 5 VDC, 0 to 23 mA (with 250 Ω resistor)
ADC Resolution 16-bit
Accuracy < 0.2% Repeatability; < 1% FSR across operating temperature range
Isolation 400 Vrms continuous / 1500 VDC for 60s (Field-to-System Ground)
Power Consumption < 11 Watts logic power
Over-Range Protection Up to 150 VDC / 115 VAC continuous

Environmental Tolerance Conditions

Operating Temperature: -20°C to +60°C (-4°F to +140°F)

Storage Temperature: -40°C to +85°C (-40°F to +185°F)

Relative Humidity: 5% to 95% (non-condensing)

Corrosion Protection: Class G3 harsh environment coating (ISA 71.04)

Vibration & Shock: Tested according to IEC 61131-2 standards

Operating Instructions

Chassis Slotting: Insert the 3723X module firmly into the dedicated I/O slot of the Tricon CX expansion chassis.

Field Wiring: Connect the field signal cables to the corresponding Tricon CX termination panel using appropriate 250 Ω resistors for 4-20 mA loops.

System Configuration: Define the input ranges (0-5 V, 4-20 mA) and HART pass-through settings in TriStation 1131 software.

Hot Swapping: To replace a fault-indicated module, insert the replacement module into the adjacent slot (if configured as hot spare) or perform an online swap directly.

Fault Diagnosis

Status indicators on the module front panel provide rapid visual diagnostics:

PASS (Green): Module passed self-diagnostics and is operating normally.

FAULT (Red): Internal fault detected on one or more TMR channels; module requires inspection or replacement.

ACTIVE (Yellow): Module is actively processing field signals.

FIELD (Yellow/Red): Field wiring or field loop fault detected (e.g., open circuit, short circuit, NAMUR NE 43 out-of-range signal).

Related Models (Tricon CX Series)

3722X: 32-Channel TMR Analog Input Module (Non-HART)

3506X: Digital Input Module (24 VDC)

3626X: Digital Output Module

3809X: Analog Output Module

3902X: Universal Input/Output Module

Storage Conditions

Store the module in its original anti-static packaging until installation.

Keep in a climate-controlled room within -40°C to +85°C and 5% to 95% non-condensing relative humidity.

Avoid direct sunlight, dust accumulation, exposure to corrosive gases, or mechanical impacts.