Eaton

Eaton XN-322-16DO-P05 Digital output modules

General specifications

Product Name

Eaton XN-322 Output module

Catalog Number

178787

Model Code

XN-322-16DO-P05

EAN

7640130098114

Product Length/Depth

104.2 mm

Product Height

16.8 mm

Product Width

80.3 mm

Product Weight

0.061 kg

Certifications

CE

cULus

UL File No.: E135462

EN 61131-2

EN 61000-6-2

EN 61000-6-4

UL508

CSA-C22.2 No. 142-M

Catalog Notes

The max. heat dissipation is specified as the maximum power produced inside the device’s housing.

Ambient conditions, mechanical

Height of fall (IEC/EN 60068-2-32) – max

1 m

Mounting position

Horizontal

Shock resistance

15 g, Mechanical, Half-sinusoidal shock 11 ms, 18 Impacts

Vibration resistance

5 – 8.4 / 8.4 -150 Hz, 3.5 mm / 1 g

Climatic environmental conditions

Air pressure

795 – 1080 hPa (operation)

Ambient operating temperature – max

60 °C

Ambient storage temperature – max

85 °C

Ambient operating temperature – min

0 °C

Ambient storage temperature – min

-20 °C

Climatic proofing

Dry heat to IEC 60068-2-2

Damp heat, constant, to IEC 60068-2-3

Environmental conditions

Condensation: prevent with appropriate measures

Relative humidity

0 – 95 % (non-condensing)

Communication

Connection type

Push-in spring-cage terminal (plug-in connection), Connection design in TOP direction

178787 - XN300 I/O system

Protocol

Other bus systems

Design verification

10.10 Temperature rise

The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.

10.11 Short-circuit rating

Is the panel builder’s responsibility.

10.12 Electromagnetic compatibility

Is the panel builder’s responsibility.

10.13 Mechanical function

The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.

10.2.2 Corrosion resistance

Meets the product standard’s requirements.

10.2.3.1 Verification of thermal stability of enclosures

Meets the product standard’s requirements.

10.2.3.2 Verification of resistance of insulating materials to normal heat

Meets the product standard’s requirements.

10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects

Meets the product standard’s requirements.

10.2.4 Resistance to ultra-violet (UV) radiation

Meets the product standard’s requirements.

10.2.5 Lifting

Does not apply, since the entire switchgear needs to be evaluated.

10.2.6 Mechanical impact

Does not apply, since the entire switchgear needs to be evaluated.

10.2.7 Inscriptions

Meets the product standard’s requirements.

10.3 Degree of protection of assemblies

Meets the product standard’s requirements.

10.4 Clearances and creepage distances

Meets the product standard’s requirements.

10.5 Protection against electric shock

Does not apply, since the entire switchgear needs to be evaluated.

10.6 Incorporation of switching devices and components

Does not apply, since the entire switchgear needs to be evaluated.

10.7 Internal electrical circuits and connections

Is the panel builder’s responsibility.

10.8 Connections for external conductors

Is the panel builder’s responsibility.

10.9.2 Power-frequency electric strength

Is the panel builder’s responsibility.

10.9.3 Impulse withstand voltage

Is the panel builder’s responsibility.

10.9.4 Testing of enclosures made of insulating material

Is the panel builder’s responsibility.

Equipment heat dissipation, current-dependent Pvid

0.25 W

Heat dissipation capacity Pdiss

0 W

Heat dissipation per pole, current-dependent Pvid

0 W

Rated operational current for specified heat dissipation (In)

0 A

Static heat dissipation, non-current-dependent Pvs

2.745 W

Electrical rating

Rated operational current (Ie)

4 A (supply input)

Rated operational voltage

24 V (terminal + 2)

160 V (terminations)

24 V (terminal +1)

Short-circuit protection

Yes, Short-circuit rating, Digital outputs

Supply voltage at DC – max

30 VDC

Supply voltage at DC – min

18 VDC

Electro magnetic compatibility

Air discharge

8 kV

Burst impulse

2 kV, Supply cable

1 kV, Signal cable

Contact discharge

4 kV

Electromagnetic fields

10 V/m at 0.08 – 1.0 GHz (according to IEC EN 61000-4-3)

1 V/m at 2 – 2.7 GHz (according to IEC EN 61000-4-3)

3 V/m at 1.4 – 2 GHz (according to IEC EN 61000-4-3)

Emitted interference

47 dB (at 230 – 1000 MHz, Class A, radiated, high frequency)

40 dB (at 30 – 230 MHz, Class A, radiated, high frequency)

Radiated RFI

10 V

Surge rating

0.5/0.5 kV, Supply cable, balanced/unbalanced), EMC

1 kV, Signal cable, unbalanced, EMC

Voltage dips

Voltage dips: 10 ms/Voltage fluctuations: Yes

Features & functions

Electric connection type

Plug-in connection

Features

Fieldbus connection over separate bus coupler possible

Fieldbus connection over separate bus coupler possible

Functions

Short-circuit protection, outputs available

General information

Current consumption

None mA (typ.), for +24 V, Power supply – Input

45 mA (typ.), for +5 V power supply (internal), Power supply – Input

Degree of protection

IP20

Mounting method

Rail mounting possible

Number of channe