SHINKAWA VM-5K DUAL VIBRATION MONITOR
MODEL VM-5K DUAL VIBRATION MONITOR
DANGER)
Alarm reset
(ALERT)
Alarm reset
(OK)
1 0 to 100μm pk-pk
1
VK-202A,
VK-202P,
FK-202F
1 5Hz or less 1 100Hz 0 Average value 0 4 to 20mADC 0 AUTO-RESET 0 AUTO-RESET 0 AUTO-RESET
2 0 to 125μm pk-pk 2 9.5Hz Seismic filter
*1 2 500Hz 1 pk to pk 1 1 to 5VDC 1 SELF-HOLD 1 SELF-HOLD 1 SELF-HOLD
3 0 to 200μm pk-pk 3 14Hz Seismic filter
*1 3 1kHz 2 rms
(additional spec./RMS) 2
Output card
/IS or /RE
option
4 0 to 400μm pk-pk 2 VK-302P,
FK-302F
4 15Hz Seismic filter
*1 4 4kHz
5 0 to 500μm pk-pk 5 40Hz(36dB/oct)
Pipe filter
*1
5 10kHz
6 0 to 3mils pk-pk
3
VC Series
Voltage
output only
7 0 to 5mils pk-pk 6 60Hz(36dB/oct)
Pipe filter
*1
8 0 to 10mils pk-pk
A 0 to 15mils pk-pk
Relay mode
(DANGER)
Relay mode
(ALERT)
Relay mode
(OK)
Alarm delay time
(DANGER)
Alarm delay time
(ALERT) Alarm output type First out*2
0 NORMALLY
DE-ENERGIZED 0 NORMALLY
DE-ENERGIZED 0 NORMALLY
DE-ENERGIZED
0 3 sec. 0 3 sec. 1 CH1 : 2 points (DANGER1,ALERT1)
CH2 : 2 points (DANGER2,ALERT2)
0 OFF
1 1 sec. 1 1 sec. 1 ON
1 NORMALLY
ENERGIZED 1 NORMALLY
ENERGIZED 1 NORMALLY
ENERGIZED
2 6 sec. 2 6 sec.
2
CH1 : 4 points (DANGER1,DANGER2,
ALERT1,ALERT2)
CH2 : None
3 None 3 None
3 Special alarm logic(option)
rms. rectification Isolate output Recorder option
output
Input power supply
requirements
Tropical
spec.
Sensitivity
correction
Special alarm logic
DANGER ALERT
1CH 2CH 1CH 2CH
When rectification code 2
is selected, specify this
option code.
0 4 to 20mADC 2 0 to -10VDC 0 85 to 264VAC 1 TIIS(IEC)
1
>DANGER >DANGER >ALERT >ALERT
1 1 to 5VDC 3 0 to 10VDC 1 24VDC 2 FM >DANGER NOT OK >ALERT <ALERT
2 0 to -10VDC 4 0 to -5VDC 2 110VDC 4 CSA NOT OK >DANGER <ALERT >ALERT
3 0 to 10VDC 5 0 to 5VDC 5 ATEX >ALERT NOT OK
4 0 to -5VDC NOT OK >ALERT
5 0 to 5VDC
2
>DANGER >DANGER >ALERT >ALERT
>DANGER >ALERT >ALERT <ALERT
>ALERT >DANGER <ALERT >ALERT
>DANGER NOT OK >ALERT NOT OK
NOT OK >DANGER NOT OK >ALERT
ALARM SET VALUE DANGER1 :
ALERT1 :
DANGER2 :
ALERT2 :
Unless specified otherwise, preset to :
DANGER : 100% of monitor range
ALERT : 90% of monitor range
ALARM INDICATOR DANGER : (red LED)
ALERT : (yellow LED)
ABNOR. ALARM
INDICATOR
OK : (green LED)
BYPASS INDICATOR BYPASS : (red LED)
TRANSDUCER INPUT VK-202A,VK-202P,FK-202F,VK-302P,FK-302F,VC Series
Number of input points : 2 points
SEQUENCE SET
VALUE
(to increase alarm set
value during operation
of the sequence circuit)
: ×1.0 to 10.0 (×0.1 step)
Preset to ×1.0 unless specified otherwise.
CAUTION : Set the alarm set value so that its designated
multiple is within 110% of the measurement
range during operation of the sequence circuit.
If set to more than 110%, alarm may not be
output.
INPUT IMPEDANCE Approx. 50k
EXTERNAL CONTACT
INPUT
(FROM REAR PANEL)
Contact type : Dry contact
Contact for external reset
Contact for sequence
BAR GRAPH METER Recorder output conversion accuracy ± 2.5% of F.S.
DIGITAL METER Recorder output conversion accuracy ± 1.0% of F.S.
RECORDER OUTPUT
CONVERSION
ACCURACY
± 0.5% of F.S. at 100Hz at 25°C (77°F REF.)
± 2.0% of F.S. at 100Hz at 0 to 65°C (32 to 149°F REF.) SUPPRESSION
FUNCTION SET VALUE
: 0.0 to 10.0 % of monitor range (0.1 % step)
Preset to 2.0 % unless specified otherwise.
CAUTION : When the measurement value is not more than
suppression function set value, indication and
recorder output value shall be as 0 %.
RECORDER OUTPUT
(FROM REAR PANEL)
Voltage or current output proportional to monitor range
1 to 5VDC (output impedance : 250)
4 to 20mADC (max. load resistance : 500)
0 to -10VDC*,0 to 10VDC*,0 to -5VDC*,0 to 5VDC*
(output impedance : 100) (*option)
Number of output points : 2 points
Standard Specifications
ALARM SET POINT 4 points (DANGER1,ALERT1,DANGER2,ALERT2) MONITOR OUTPUT
(FROM FRONT, REAR
PANEL)
Input signal is output via a buffer amplifier.
Signal level : -0.8 to -22VDC(VK), 0 to 5VDC(VC)
Output impedance : 100 (load resistance 50k or more)
ALARM SET RANGE 0 to 110% of monitor range
ALARM SET
ACCURACY
± 1.0% of F.S. or less
TEMPERATURE
RANGE
Operating temperature : 0 to 65°C (32 to 149°F REF.)
Storage temperature : -30 to +85°C (-22 to +185°F REF.)
Relative humidity : 20 to 95% (noncondensing)
ALARM SET
REPEATABILITY
± 0.1% of F.S. or less
ALARM OUTPUT 5 points (DANGER1,ALERT1,ALERT2,DANGER2,OK) or
6 points (DANGER1,ALERT1,ALERT2,DANGER2,OK1,OK2)
MATERIAL AND FINISH Face plate : Aluminum Munsell N-4.0 (equiv.)
MASS
Monitor : max.0.7kg (max.1.6lb REF.)
(including single unit instrument rack : max.2.5kg (max.5.5lb REF.))
MEASURED
VIBRATION VALUE
LCD digital meter with 5 digits (7 segments, with