SHINKAWA MODEL VM-5D DUAL DIFFERENTIAL
MODEL VM-5D DUAL DIFFERENTIAL
EXPANSION MONITOR
Monitor range Input signal Frequency
response Polarity*1 Recorder output Alarm reset
(DANGER)
Alarm reset
(ALERT)
Alarm reset
(OK)
1 -5 to 0 to +5mm 1 VK-143P,FK-143F 0 DC to 0.5Hz 1 Direct 0 4 to 20mADC 0 AUTO-RESET 0 AUTO-RESET 0 AUTO-RESET
2 0 to 10mm 2 VK-263P,FK-263F 2 Reverse 1 1 to 5VDC 1 SELF-HOLD 1 SELF-HOLD 1 SELF-HOLD
3 -10 to 0 to +10mm
3
VC Series
Voltage
output only
2
Output card
/IS or /RE
option
4 0 to 20mm
5 -0.25 to 0 to +0.25inch
6 0 to 0.5inch
7 -0.5 to 0 to +0.5inch
8 0 to 1.0inch
Relay mode
(DANGER)
Relay mode
(ALERT)
Relay mode
(OK)
Alarm delay time
(DANGER)
Alarm delay time
(ALERT) Alarm output type First out*2
0 NORMALLY
DE-ENERGIZED 0 NORMALLY
DE-ENERGIZED 0 NORMALLY
DE-ENERGIZED
0 3 sec. 0 3 sec. 1 CH1 : 2 points (DANGER1,ALERT1)
CH2 : 2 points (DANGER2,ALERT2)
0 OFF
1 1 sec. 1 1 sec. 1 ON
1 NORMALLY
ENERGIZED 1 NORMALLY
ENERGIZED 1 NORMALLY
ENERGIZED
2 6 sec. 2 6 sec.
2
CH1 : 4 pionts (H-DANGER,H-ALERT,
L-ALERT,L-DANGER)
CH2 : None
3 None 3 None
Isolate output Recorder option
output
Input power supply
requirements*3
Tropical
spec.
Sensitivity
correction
0 4 to 20mADC 2 0 to -10VDC 0 85 to 264VAC 2 FM
1 1 to 5VDC 3 0 to 10VDC 1 24VDC 4 CSA
2 0 to -10VDC 4 0 to -5VDC 2 110VDC 5 ATEX
3 0 to 10VDC 5 0 to 5VDC
4 0 to -5VDC
5 0 to 5VDC
ALARM SET VALUE H-DANGER1 :
H-ALERT1 :
L-ALERT1 :
L-DANGER1 :
H-DANGER2 :
H-ALERT2 :
L-ALERT2 :
L-DANGER2 :
Unless specified otherwise, preset to :
H-DANGER : 100% of monitor range
H-ALERT : 90% of monitor range
L-ALERT : 10% of monitor range
L-DANGER : 0% of monitor range
ALARM INDICATOR DANGER : (red LED)
ALERT : (yellow LED)
ABNOR.ALARM
INDICATOR
OK : (green LED)
BYPASS INDICATOR BYPASS : (red LED)
TRANSDUCER INPUT VK-143P,FK-143F, VK-263P,FK-263F, VC Series
Number of input points : 2 points
INPUT IMPEDANCE Approx.50kΩ
EXTERNAL CONTACT
INPUT
(FROM REAR PANEL)
Contact type:Dry contact
Contact for external reset
BAR GRAPH METER Recorder output conversion accuracy ±2.5% of F.S.
ZERO SHIFT 0 to 100% of monitor range
OTHERS
DIGITAL METER Recorder output conversion accuracy ±1.0% of F.S.
RECORDER OUTPUT
CONVERSION
ACCURACY
±0.5% of F.S. at 25°C
±2.0% of F.S. at 0 to 65°C
Standard Specifications
RECORDER OUTPUT
(FROM REAR PANEL)
Voltage or current output proportional to monitor range
1 to 5VDC (output impedance : 250Ω)
4 to 20mADC (max. load resistance : 500Ω)
0 to -10VDC*,0 to 10VDC*,0 to -5VDC*,0 to 5VDC*
(output impedance : 100Ω) (*option)
Number of output points : 2 points
ALARM SET POINT 8 points (H-DANGER1,H-ALERT1,L-DANGER1,L-ALERT1,
H-ALERT2,H-DANGER2,L-ALERT2,L-DANGER2)
ALARM SET RANGE -10 to +110% of monitor range
ALARM SET
ACCURACY
±1.0% of F.S. or less
MONITOR OUTPUT
(FROM FRONT, REAR
PANEL)
Input signal is output via a buffer amplifier.
Signal level : -0.8 to -22VDC(VK), 0 to 5VDC(VC)
Output impedance : 100Ω (load resistance 50k or more) ALARM SET
REPEATABILITY
±0.1% of F.S. or less
ALARM OUTPUT 5 points (DANGER1,ALERT1,ALERT2,DANGER2,OK) or
6 points (DANGER1,ALERT1,ALERT2,DANGER2,OK1,OK2)
(H,L are OR output)
TEMPERATURE
RANGE
Operating temperature : 0 to 65°C (32 to 149°F)
Storage temperature : -30 to +85°C (-22 to +185°F)
Relative humidity : 20 to 95% (noncondensing)
MEASURED VALUE LCD digital meter with 5 digits (7 segments, with back light)
LCD bar graph meter (40 segments, with back light)
* Measurement value and alarm set value are indicated on
the digital meter and bar graph meter simultaneously.
MATERIAL AND
FINISH
Face plate : Aluminum Munsell N-4.0 (equiv.)
MASS Monitor : max.0.7kg
(including single unit instrument rack : max.2.5kg)