RS-232 front panel port by use of the PowerPort Windows based

or PowerNetTM Software program. This subject is discussed in

more detail later in the manual.

2.5.5  Functions Which Must be Programmed

As stated earlier the FP-5000 comes pre-configured with default

or factory settings. The phase and ground overcurrent functions

are the only protection functions enabled and the current and

voltage unbalanced functions are the only alarm functions

enabled.  All other protection and alarm functions are turned off

and must be set to enable their operation. The I/O comes pre

configured as default from the factory for the most common

applications. The I/O can be changed per the requirements of the

user’s application.  The current and voltage unbalanced alarms

(46-2 and 47-2) are enabled to assist the user in diagnosing any

wiring problems.

For now we assume that the default settings will be adequate

except for the following list of functions, which the user must

program in order to handle the specific characteristics of your

system. Since only one protection setting Group is enabled, we

need only program the one group of protection settings and the

values necessary to define the proper operating environment of

the FP-5000. Please refer to Table 4 – Minimum List of Functions

Which MUST be Programmed for those items

We will only be concerned with System Config and Protection

settings within the Quick Start section of this manual.

Select the category and press the Enter pushbutton to proceed.

The actual setting of values will be covered in Section 2.5.5.

2.5.4  Minimum Program Requirements

Default settings are provided to minimize the number of manual

programming steps for typical applications. For more complex

applications cases, the use of computer generated setting files

simplifies the setting process. The user programs through the

Table 4. Minimum List of Functions Which MUST be Programmed.

Setting Main

System Config

Protection

System Alarms

Logging

Contact Input CFG

Output Config

Programmable Logic

Cold Load Pickup

Clock

Communications

Change Password

SETTING DEFAULT SETTING INCR DISPLAY USER SETTING

System Configuration

Frequency: 60 List 50 Hz or 60 Hz

Phase Seq: ABC List ABC or ACB

CT Connect: 3-wire List 3-wire, 4CT In, 4CT Ig

PH CT Ratio: 500:Inom 3 1 I nom to 6000:CT, where CT is 1 or 5 A based on CT board

jumper

NU CT Primary 500:Inom 3 1 Inom to 6000:CT, where CT is 1 or 5 A based on CT board

jumper

VT Connect: Wye List Wye or Delta

Main VTR: 100 1 1 to 8000

Aux VTR: 100 1 1 to 8000

VT Secondary Rating: 69.28 1 50 to 250 V

TOC Reset Time “TOC Reset T” 5 1 1-20 Cycles

Protection/Group 1

Phase Overcurrent

51P PH TOC Shape: MOD List IT, I2T, I4T, FLAT, MOD, VERY, XTRM, IECA, IECB, IECC

51P PH TOC Reset: Calc List Inst, Calc, T Delay

51P PH TOC Direction: Both List Forward, Reverse, Both

51P PH TOC Pickup: 1.00 0.01 0.1 to 4.0pu or Disable

51P PH TOC Time Mult: 1.00 0.01 0.05 to 10.0

50P-1 PH IOC Pickup: 2.00 0.01 0.1 to 20.0pu or Disable

50P-1 PH IOC Delay (c): 0 1 0 to 9999 cycles

50P-1 PH IOC Direction: Both List Forward, Reverse, Both

50P-2 PH IOC Pickup: 3.00 0.01 0.1 to 20.0pu or Disable

50P-2 PH IOC Delay (c): 15 1 0 to 9999 cycles

50P-1 PH IOC Direction: Both List Forward, Reverse, Both