The optional Touchscreen and Trackball are not to be used together on the same US, so
they share the same connector (J1) on the EPDGP I/O card. When the Trackball or
Touchscreen is selected are bulkhead connected at the transition panel (see Figure 2-7).
1. The cables from the optional touchscreen pass through the clamps in the left location
marked TOUCHSCREEN on the lower transition panel in Figure 2-5. and are to be
connected to the EPDGP I/O card in slot 2 as shown in Figure 2-6.
2. Plug the large connector into J1. marked TOUCHSCREEN or TRACKBALL in Figure
2-6. on the EPDGP I/O card and the small connector into J4. marked POWER in
Figure 2-6. The EPDGP I/O card may have to be partially or completely pulled out to
make these connections. Use proper board handling precautions, including a grounded
wrist-strap, to extract the card. Use care not to disturb or dislodge existing cables and
then firmly reseat the card.
3. Using a cable-tie (51190879-001) on each cable, fasten the cables to their strain-relief
clamps on the upper transition panel.
2.7.11 Trackball Cabling
The cable from the optional trackball is to be connected to the lower transition panel at the
left location marked Trackball in Figure 2-5. Use a small screwdriver to tighten the screws
(2) on the connector. In accordance with the user’s preference, place the trackball either to
the right or left side of the keyboard
If your Enhanced Micro TDC3000 System has one color monitor and no options except a
touchscreen or trackball, there is no further cabling to be done on tower #2. Skip this
section and proceed with subsection 2.10. Installation Wrap-Up.
If you have a second Universal Station or additional options, consult the paragraphs in this
section that deal specifically with those options and cable them accordingly.
The following subsections, where applicable, may contain information on the EMC
| Triconex | 3704E |
| Triconex | 3504E |
| Triconex | 3504E |
| EMERSON | 1X00781H01L |
| EMERSON | PR6423 009-041+CON 041/913-030 |
| KONSGBERG | RCU500 |
| KONSGBERG | RMP400 |
| KONSGBERG | RDIOR400 |
| Cutler Hammer | 1775K PMPP1700 |
| MOORE INDUSTRIES | MDS/PRG/10-30DC/-MAO |
| ABB | DHH805-A |
Directive that affects the hardware. When applicable, the EMC hardware information will
usually follow the hardware that is not in compliance with the directive.
2.8.1 Optional Universal Station Upgrade
Adding this kit upgrades a basic Enhanced Micro TDC3000 System. This involves
adding a Universal Station node containing K2LCN, EPDG2. EPDGC I/O boards, and
keyboard. The monitor is ordered separatly. Refer to MX-MTUS34 or MX-MTUS36
Upgrade Kit Installation Instructions for directions for upgrade.
2.8.2 Optional Redundant Network Interface Module
The redundant NIM, in conjunction with a redundantly-connected Advanced Process
Manager, provides a level of protection in case of equipment failure
Ref. #
Cabling for the Universal Station is shown in the following figure and table.
Application Notes
51192126-200 Video Cable
51308099-100 Mouse/Trackball Interface Cable
Not Applicable
51308103-003 Printer Cable – 3 meters/9.8 ft.
51308103-008 Printer Cable – 8 meters/26.3 ft.
51308103-015 Printer Cable — 15 meters/49.2 ft.
51192054-101 Cable,SCSI Shielded, 50 position
51305070-200 Cable, SCSI
51308110-100 Cartridge DC Power Cable
51308109-100 Cartridge DC Power Cable (in Enclosure)
51308105-200 Keyboard Interface Cable
51308104-100 Keyboard Interface Cable (in Keyboard Tray)
51304496-046 Engineer”s Keyboard Cable (in Keyboard Tray)