Honeywell

Honeywell TDC‑3000 BASIC,Extended Controller(TDC‑2000 DHW),4DP7AXA102

TDC‑3000 BASIC,Extended Controller(TDC‑2000 DHW),4DP7AXA102

The optional Touchscreen and Trackball are not to be used together on the same US, so

they share the same connector (J1) on the EPDGP I/O card.  When the Trackball or

Touchscreen is selected are bulkhead connected at the transition panel (see Figure 2-7).

1. The cables from the optional touchscreen pass through the clamps in the left location

marked TOUCHSCREEN on the lower transition panel in Figure 2-5. and are to be

connected to the EPDGP I/O card in slot 2 as shown in Figure 2-6.

2. Plug the large connector into J1. marked TOUCHSCREEN or TRACKBALL in Figure

2-6.  on the EPDGP I/O card and the small connector into J4. marked POWER in

Figure 2-6.  The EPDGP I/O card may have to be partially or completely pulled out to

make these connections.  Use proper board handling precautions, including a grounded

wrist-strap, to extract the card.  Use care not to disturb or dislodge existing cables and

then firmly reseat the card.

3. Using a cable-tie (51190879-001) on each cable, fasten the cables to their strain-relief

clamps on the upper transition panel.

GE SBI-PDP-32
GE IC693CMM321
GE IC200ALG263
GE IC693CMM321
A-B 2090-K6CK-D44M
A-B 2094-EN02D-M01-S1
A-B 2094-BC07-M05-M
ABB ACS510-01-157A-4
A-B 5069-FPD
Rosemount 3144PD6A1K1B5M5QTHR7/214CRTSMA1S3M0350SLK1SR1C1UAE065TB
GE SBI-PDP-32
KEBA CP505A
A-B 5069-FPD
ABB FPBA-01
ABB RV5/50 24-50V
西德福 SFIE4R24
ALSTOM UMT 162 CS-C3
BENDER iso685-D-B-CN
Emerson M700-03400025A
ABB 560PSU02 1KGT011900R0001
ABB 560PSU02 1KGT011900R0001
NI PCI-4472

2.7.11 Trackball Cabling

The cable from the optional trackball is to be connected to the lower transition panel at the

left location marked Trackball in Figure 2-5.  Use a small screwdriver to tighten the screws

(2) on the connector.  In accordance with the user’s preference, place the trackball either to

the right or left side of the keyboard

cables are clearly marked “A” and “B.”

1. Connect these UCN cables to their proper connectors on the lower transition panel (see

Figure 2-5).  BE SURE “A” AND “B” CABLES CONNECT RESPECTIVELY TO THE “A”

AND “B” CONNECTORS on the panel bracket without cross-connection.  If necessary,

check the mini-coax cables from the rear of the panel bracket to the NIM MODEM card

to allow you to confirm the connections.

2. Route the UCN drop cables from the panel out of the cabinet without making sharp

bends or kinks in the cables.

3. Connect a ground wire from the two UCN taps serving this NIM to the screw marked

UCN GND in Figure 2-5.

4. The NIM MODEM card has been factory-pinned to UCN address #1.  You will verify

this address in Section 4 of this manual.  Consult UCN manuals listed in subsection

1.5 for installation and pinning of the Advanced Process Manager that this NIM “talks”

to.  The PMM in that Advanced Process Manager must be pinned for UCN address #3

Table 2-2 — Micro TDC 3000 Cabling — Standard (Trackball)

Ref. #

Cabling for the Universal Station is shown in the following figure and table.

Application Notes

51192126-200 Video Cable

51308099-100 Mouse/Trackball Interface Cable

Not Applicable

51308103-003 Printer Cable – 3 meters/9.8 ft.

51308103-008 Printer Cable – 8 meters/26.3 ft.

51308103-015 Printer Cable — 15 meters/49.2 ft.

51192054-101 Cable,SCSI Shielded, 50 position

51305070-200 Cable, SCSI

51308110-100 Cartridge DC Power Cable

51308109-100 Cartridge DC Power Cable (in Enclosure)

51308105-200 Keyboard Interface Cable

51308104-100 Keyboard Interface Cable (in Keyboard Tray)

51304496-046 Engineer”s Keyboard Cable (in Keyboard Tray)