1.2.2  After Startup

1. Continue your “no-smoking” rule in the operating area.  Smoke and fine dust particles

can damage cartridge disks and drives.

2. Maintain humidity levels (ideally) between 40 and 60% (lower humidity may cause

static-discharge problems).

3. Control humidity fluctuations to a rate-of-change less than 6% per hour.

4. Do not defeat temperature and humidity controls by opening doors and windows (for

example, to enhance operator comfort).

5. Keep traffic in the control-room operating areas to a minimum.  Restrict access to

authorized personnel, whose duties require control room entry.

6. Review procedures for extinguishing electrical fires and establish fire-fighting

procedures.  Refer to a qualified fire-fighting systems contractor for assistance

Plant personnel frequently use hand-held radios (“walkie-talkies”), or citizens-band

radios mounted in maintenance vehicles, for communications.  To avoid RFI problems,

review the following:

ABB AI625
BENTLY 3500/42M
BENTLY 3500/40M
BENTLY 3500/33
GE IS230TSVCH1A
GE IS220PTCCH1A
GE IS220PPRAS1B
Meggitt MPC4 200-510-074-114
Pioneer Magnetics PM2722-1 24F33-0-4-R-S
ABB DSPC172H 57310001-MP
Metrix 5485C‑007‑046
ABB REF615Z HCFZAEADABCZDAA11G
Hirschmann OZDProfi12MG12 943727‑321
ABB REF630 UBFNABABAAAZANEBXC
WOOODWARD 5417-557
GE H201CI-1
ABB 3BHL000389P0104 5SHX2645L0004

• If radio communications must take place within an operating area or process

controller area, a base-station transceiver with an external antenna should be

used.

• For other applications, radio transmitters with outputs rated as high as 5 watts

must be kept at least 3 meters (10 ft.) from the Enhanced Micro TDC3000

equipment during operation.  Transmitters with outputs higher than 5 watts

must be kept as far as possible from your equipment.  Keep equipment doors

closed while operating.

Other sources of RFI include generators, arcing relays, or motor contacts, etc.

8. Follow proper cleaning procedures when cleaning the operator area or the control room:

• Do not use water freely.  Mop should be only dampened, not wet or dry.

• Use a lint-free, antistatic-type dust cloth to remove dust.

• Do not sweep around areas containing cartridge disks or drives.

• Use a vacuum cleaner on carpets—preferably one connected to an external

system.

• Do not allow liquids to be placed on the Enhanced Micro TDC3000 keyboards

and equipment.  Liquid spills will damage electronic components