During normal operation, the ConnectUPS Card controls the

communication path to the UPS and allows network-based access to

UPS data through the Web and SNMP. Some situations require direct

serial communication to the UPS in a pass-through mode, such as:

The UPS firmware requires a field upgrade with a 9600 baud serial

port connection to the UPS.

The user wants to run a local copy of LanSafe software with serial

communication to the UPS.

The card’s Normal mode of operation must be disabled for Serial

Pass-Through mode to be available.

Reconfiguring the Card for Serial Pass-Through Mode

NOTE  In Serial Pass-Through mode, communication through the ConnectUPS Card Ethernet

port stops, and any existing connections (such as to NetWatch software clients or SNMP

management tools) cease. However, the Ethernet switch functionality of the ConnectUPS

Card continues to function.

The following steps disable Normal mode by changing the switches on

the ConnectUPS Card and restarting the card in Serial Pass-Through

mode.

MITSUBISHI ENGINE OPERATOR CONTROL CIRCUIT NF400-SEW 400AMPS

Telemechanics TSXT3170 Terminal T317 connects only T317 terminal line

Festo CMMP-AS-C5-3A 550042

ABB AX411/11104

SCHNEIDER ELECTRIC OTB1E0DM9LP Ethernet TCP/IP

Schneider Electric STBNIP2311

Siemens 6AU1432-2AA00-0AA0

SIEMENS 6SL3224-0BE22-2AA0

ALLEN-BRADLEY 22B-A5P0N104

Atlas Copco D313-DL-ADVANCED

Contraves Varidyn Compact ADB/V190.45 Servo Controller 13KVA GB402.878-V

KIMO MotorMaster MM 2.2FMC-emc

GRUNDFOS – SCAN MESSTECHNIC D-320-GF1-230 / DID-1 TI1-CND

QGEORGIN REGULATOR DFML10B

Kl枚ckner Moeller | Compact Automation Device | PS3-DC-EE

KEB 10.F0.220-3429 4.0KVA 2.2KW

KEB Combivert 11.F0.R11-3429 94352753/106824 5.2KVA 3KW

PR1555 Philips PR1555/00 Digital Weight Display Board

PR1628 Philips PR1628/60 Control Panel

IKUSI TM70/2.21

Siemens Contactor 3TF52 3TF5222-0AF0

770-500-002 MECMAN IPC 500S PROGRAM LOADER 4K INDUSTRIAL PROGRAMMABLE CONTROLLER

KIMO ELECTRIC 11S2-27

KIMO SCM1-12 Safety Control Module 1

ABB 1SCA022753R3800 OS400D12

To reconfigure the card for Serial Pass-Through mode:

1. Note the current position of DIP switches on the card [the default

setting for both switches is the 0 (off) position]. Write them here for

later reference.

DIP Switch 1  _____ 0 (off)   _____ 1 (on)

DIP Switch 2  _____ 0 (off)   _____ 1 (on)

2. Set both DIP switches to the 1 (on) position for Serial Pass-Through

mode

Using a pen or paperclip, press the RESET switch on the card to

restart the card in the Serial Pass-Through mode.

4. Locate the configuration cable (labeled “PC”) that was supplied

with the ConnectUPS Card.

5. Plug the RJ-45 end of the configuration cable into the COM port on

the card.

Verify that you have used the port labeled “COM.” The other ports

on the card will not work for configuration.

6. Plug the other end of the configuration cable into the serial COM

port on the computer.

7. Set up the PC to communicate with the UPS serially:

Open your terminal emulation program (such as HyperTerminal®).

Select the appropriate serial connection (such as COM1).

Set the serial line to 9600 baud, No parity, 8 data bits, 1 stop bit,

and no flow control.

Returning the Card to Normal Operation

After using the card in Serial Pass-Through mode, restart the card in

Normal mode:

1. Disconnect the configuration cable from the card and PC.

2. Return the card’s switches to the original settings noted in Step 1

on page 32.

3. Using a pen or paperclip, press the RESET switch on the

ConnectUPS Card to restart the card in Normal mode.