Eaton 5P650iR UPS power supply
Select Open next to Filename and select the binary upgrade file that
was previously downloaded or otherwise received and copied to the
PC.
Select Upgrade to start the process. After the process starts, do not
cancel or interrupt the upgrade process. Otherwise, the
ConnectUPS Web/SNMP Card receives a corrupted image,
preventing the card from operating correctly.
8. When the Firmware Upgrade Utility completes, exit the program by
selecting Quit and then answering Yes to confirm.
External Contact Monitoring Feature
The status of the two user-provided contact devices is monitored via
pins on the ConnectUPS Card COM (configuration) port and reported
several different ways:
SNMP – via the PowerMIB, the card sends traps indicating the active
or inactive state of the contact.
E-mail notification – if this feature has been configured on the
ConnectUPS Card, the specified recipients receive an e-mail
whenever the contact status changes. The body of the e-mail
contains the Contact Number, Contact Type, Contact State, and
Contact Description.
If these recipients have been configured to receive notification of
“All” event levels via e-mail, they also receive notification whenever
the contact monitoring is enabled or disabled and when the contact
monitoring cable is installed or removed.
ConnectUPS Card Web pages – the Summary and Status@aGlance
pages reflect the change in state of the contact. The Event Log is
updated with all External Contact Monitoring-related messages,
including the Contact Number to assist with identification of the
contact

Cabling
To use the Contact Monitoring features, construct a cable with an RJ-45
connector that will plug into the ConnectUPS Web/SNMP Card COM
(configuration) port.
You can use a CAT5 Ethernet cable and remove the other RJ-45
connector. Only four of the eight wires present in the cable are required
to connect the two contact devices. See Figure 12 and Table 6 to
construct the cable