VIBRO-METER

Vibro-Meter CPU controller   CPUM Mk2    600-050

CPU controller    CPUM Mk2    600-050

Status indicators (LEDs)

IN :Green indicates that the external mains supply is present and is

within the normal range.

See Mechanical drawings – VM600Mk2 versions on page 7 and

Mechanical drawings – VM600 versions on page 8.

+5V :Yellow indicates that the +5 VDC supply is being generated and is

within the normal range

+12V :Yellow indicates that the +12 VDC supply is being generated and is

within the normal range

−12V :Yellow indicates that the −12 VDC supply is being generated and is

within the normal range

Connectors

Rear : Two high-current DIN 41612 type H15 connectors.

Sharing of power supply voltages and signals via the VM600Mk2/

VM600 rack backplane (ABE04x).

Physical

Dimensions : See Mechanical drawings – VM600Mk2 versions on page 7 and

Mechanical drawings – VM600 versions on page 8

Weight : 2.4 kg (5.3 lb) approx

The table below shows the maximum permissible duration of an interruption (cut) to the external AC or DC

mains supply used as the input voltage to an RPS6U rack power supply.

The maximum duration values depend on the maximum combination load for the RPS6U rack power supply,

the number of RPS6U rack power supplies installed in the rack and the number of modules (cards) installed in

the VM600Mk2/ VM600 rack (the actual load). If an interruption lasts longer than the maximum permissible

duration, then the VM600Mk2/ VM600 modules (cards) installed in the rack may reset.

Maximum duration of interruption

to the supply input (ms)

At 10 % of

combination load

At 100 % of

combination load

One RPS6U AC rack power supply in the rack 190 10

Two RPS6U AC rack power supplies in the rack 250 20

One RPS6U 24 DC rack power supply in the rack 75 7

Two RPS6U 24 DC rack power supplies in the rack 150 14

One RPS6U 110 DC rack power supply in the rack 190 10

Two RPS6U 110 DC rack power supplies in the rack 250 20

SPECIFICATIONS

Supported sensors

Sensor inputs

Dynamic inputs

Number of channels

Voltage inputs

• DC measurement range

• AC measurement range

• AC + DC measurement range

Common-mode voltage range

Common-mode rejection ratio (CMRR)

Current inputs

• DC measurement range

• AC measurement range

• AC + DC measurement range

Frequency bandwidth

Input impedance

•Voltage

•Current

Measurement accuracy

•Amplitude

•Phase

•DC

Dynamic input range

DC filtering

DC filter

• Cutoff frequency (−3 dB)

• Roll-off

: Compatible with a wide range of sensors and measurement chains with

current (2-wire) or voltage (3-wire) outputs, including the following

sensors from the Parker Meggitt vibro-meter ® product line:

• CAxxx vibration sensors (piezoelectric accelerometers)

• CExxx and PVxxx vibration sensors (piezoelectric accelerometers

and velocity sensors)

• CVxxx and VExxx vibration sensors (velocity sensors)

• CPxxx dynamic pressure sensors (piezoelectric pressure sensors)

• TQxxx proximity sensors

• LSxxx air-gap sensors.

: 4 (independent channels)

: 0 to +20 VDC or 0 to −20 VDC.

Note: 10 Hz DC filter (see DC filtering on page 9).

: ± 20 VPEAK-PEAK

: ± 24 VPEAK-PEAK

: −50 to +50 VDC

: > 55 dB, up to 60 Hz.

> 60 dB, from 45 to 65 Hz.

: 0 to 35 mA.

Note: 10 Hz DC filter (see DC filtering on page 9).

: ± 30 mA PEAK-PEAK

: ± 50 mA PEAK-PEAK

: DC to 20 kHz

: ≥ 100 kΩ, between the differential (high and low) inputs

: 200 Ω ± 0.2 %

: ±1 % of full scale

: ±1° from 10 Hz to 2 kHz.

±15 ° from 2 to 20 kHz.

: ± 0.85 % of full scale for voltage inputs (0 to 10 VDC ).

± 1.25 % of full scale for current inputs (0 to 20 mA).

: ≥ 80 dB, from 3 Hz to 20 kHz

: 10 Hz ± 3.5 Hz

: −40 dB/decade (second order)

Note: The DC filter is used to extract the DC part of a dynamic input when it is configured as a DC input.