Vibro-Meter ABE044 – 6U 19-inch rack (with expansion slots)
ABE044 – 6U 19-inch rack (with expansion slots)
Channel inhibit function
The channel inhibit function allows individual AMC8 channels to be temporarily bypassed,
that is, it temporarily inhibits the protection offered by any associated relays.
The channel inhibit function is intended to allow a component in a measurement system
front-end, such as a sensor/transducer or signal conditioner, to be replaced for an individual
channel while the other machinery monitoring channels and functions continue to operate as
normal.
This allows the machinery being monitored to continue to operate (if the protection offered by
the other machinery monitoring channels and functions is adequate). It also allows any
control system using the relays to avoid false trips during such maintenance activity.
When the channel inhibit function is activated for an AMC8 channel:
• The channel continues its processing as per its configuration but inhibits the protection
offered by any associated relays.
This allows the effect of any changes to the measurement system front-end to be
observed. In this way, it can also be ensured that there are no ongoing alarm conditions
before the de-activation of the channel inhibit.
• Any DCoutput functionality associated with the channel continues, if enabled.
• The following flags (bits) for the channel processing are forced to a known state:
• The error bit (Err), OK system check (SOK), alarm (A+, A−) and danger (D+, D−)
flags are all forced to a normal state (which is false, that is =0).
The sensor bypassed (SBP) flag and the global channel OK fail flags are also set
active.
NOTE: The VM600 MPS1 and VM600 MPS2 software packages use the SBP (sensor
bypassed) flag to refer to the channel inhibit function.
• Any processing channels that depend on the channel are automatically bypassed.
• The channel’s status indicator (LED) on the panel of the AMC8 card slowly blinks green
for the duration of the channel inhibit (approximately once per second).
When the channel inhibit function is de-activated for an AMC8 channel, the card:
• Waits 12seconds for signal stabilisation (total recovery time).
• Resets (clears) any latched alarms.
• Stops forcing the flags for the channel processing to a normal state, so that the true
status of the machinery monitoring system is returned again. The sensor bypassed
(SBP) flag is also set inactive
1OK system checking
The OK System monitors the input signal from the sensor in order to verify if the sensor is
connected and operating normally. To do this, the DC signal level is compared against two
user-configurable OK levels: a minimum normal level and a maximum normal level.
Any problem with the transducer and/or signal conditioner or connecting cable that causes
the signal to deviate beyond these OK levels will cause an individual alarm for the input
channel (corresponding to the individual GlobalChannelOK bit).
As shown in Figure5-5:
• The “confirmation time” is a fixed firmware time delay used so that only an input signal
that is outside the configured OK levels for a time period greater than 250 ms is detected
as an OK system failure. This is used to ensure that noise (“spikes”) on the DC signal
level are not accidentally recognised as failures.
• The “response time” is the maximum time delay from the time that an OK system failure
is detected until the corresponding alarms are set (GlobalChannelOK bit for the input
channel). The actual time delay depends on the processor load of the card but is less
than 100ms.