SEL

SEL SEL-735 Power Quality and Revenue Meter

SEL-735

Power Quality and Revenue Meter

The SEL-735 offers high-accuracy metering combined with detailed power quality analysis. With data available at their fingertips, operators can easily identify power system anomalies and mitigate their impact.

For high-accuracy revenue metering applications, the SEL-735 exceeds ANSI C12.20 0.1 and IEC 62053-22 0.1 S accuracy class requirements over a wide current range.

The SEL-735 maintains this accuracy through its entire service life, eliminating costs associated with field calibration.

This makes the SEL-735 the premier choice for points of common coupling, interchanges, and critical loads.With optional continuous waveform streaming,

the SEL-735 precisely samples and sends waveform data from the power system at 3 kilosamples per second (ksps).

Accurate Metering

The SEL-735 exceeds the requirements of ANSI and IEC accuracy standards over a wide current range.

Capable of reliable and precise metering even in the presence of harmonics, the SEL-735 exceeds the Accuracy Class 0.1 requirements of ANSI C12.20 and 0.1 S accuracy class for IEC 62053-22.

Quality-focused manufacturing ensures that the meter will meet these accuracy requirements throughout its service life.Load Profile Data Collection

You can collect billing data with a simple-to-use load profile recorder that captures years of data.Advanced Integration

The SEL-735 integrates seamlessly into Itron MV-90 billing software, IEC 61850. DNP3. IEEE C37.

118. Modbus, or SEL communications architectures. Multiple communications ports and protocols enable the SEL-735 to simultaneously communicate with up to ten devices.IEEE C37.118.1a-2014 Synchrophasors

SEL-734 and SEL-735 Product Feature ComparisonThe SEL-734 Revenue Meter is no longer in production. SEL recommends selecting the SEL-735 in place of the SEL-734.SEL-735 Power Quality and Recording OptionsChoose from three power quality options to fit any application and budget.

Feature Basic Intermediate Advanced
General
Display Customizable three-line or single-line display Customizable three-line or single-line display Customizable three-line or single-line display; 5-inch 800 × 480 color touchscreen display*
Front Port ANSI Type II optical port or EIA-232 port ANSI Type II optical port or EIA-232 port ANSI Type II optical port or EIA-232 port; Type-C USB*
Memory 128 MB 256 MB 1 GB
Max Harmonic Order 15th 63rd 63rd
Interharmonic Quantities No No Yes
Harmonic Angles No No Yes
Power Harmonics No No Yes
Waveform Capture
Samples Per Cycle 16 16, 128 16, 128, 512
Duration (cycles) 15 15–600 15–600
Number of Events 256 33–6,200 101–10,000
COMTRADE Reports Yes Yes Yes
Wave View Oscillography No No Yes
Continuous Waveform Streaming to Synchrowave Upgradable Yes Yes
Load Profile Data
Recorders × Channels 1 × 16 12 × 16 32 × 16
Acquisition Rates 1–120 min 3–59 s, 1–120 min 3–59 s, 1–120 min
Storage Duration 0–10 years, varies with acquisition rate and number of channels used 0–20 years, varies with acquisition rate and number of channels used 0–20 years, varies with acquisition rate and number of channels used
Example Duration 10 years for 16 channels logged every 10 min 20 years for 16 channels logged every 10 min 20 years for 16 channels logged every 10 min
Voltage Sag, Swell, Interruption (VSSI) Recorder
Typical Number of Summary Events 270 270 600
Number of Detailed Rows 60,000 60,000 >130,000
Minimum Disturbance Duration 1/4 cycle 1/4 cycle 1/4 cycle
Sampling Rate 4 samples/cycle–1 sample/day, adaptive 4 samples/cycle–1 sample/day, adaptive 4 samples/cycle–1 sample/day, adaptive
Sequential Events Recorder (SER)
Number of Events >80,000 >80,000 >80,000
Number of Channels Monitored ≤72 ≤72 ≤72
IEC 61000-4-30 PQ Compliance
150/180-Cycle, 10-Minute, 2-Hour Class A Class A
Flicker Class A (10-min, 2-hr updates) Class A (1-min, 10-min, 2-hr updates)
Voltage Harmonics Class A
Current Harmonics Class A