The RCU501 is a controller module for process control purposes.

It is based on the PowerPC Host Processor MPC8245 running

at 400 MHz and with RAM memory running at 133 MHz.

The main features of the RCU501 are:

32-bit CPU running at 400 MHz

VxWorks real-time operating system

64MByteRAM

16MByteFlashmemory

4 general-purpose opto-isolated digital input channels

4 general-purpose opto-isolated digital output channels

8 Link Channel interfaces dedicated for RSER200 modules

Dual Process Net, Ethernet interfaces

(10BASE-T/100BASE-TX) for interconnecting

operator stations and controllers

Dual RedNet, Ethernet interfaces (10BASE-T/100BASE-TX)

for redundancy conÞgurations

Dual RBUS interface for connection to RIO200 and RIO420

modules

2 CANinterfaces

2 PROFIBUS DP interfaces

Built-in real-time clock

Watchdog status output

Cooling fan alarm

High temperature alarm

Over/under-voltage power alarms

Dual supply voltage (24 VDC)

Low power consumption (typical 18 W)

Built-in Test Equipment (BITE) for module monitoring during

run-time

Run/Error status LED

Eight test status LEDs

Compliant to standards IEC 60945 and IACSE10

RCU501 is a Remote Controller Unit (RCU) based on a

PowerPC andremote I/O-bus interfaces. It runs the application

program of a process control system and interfaces to different

bus systems. RCU501 is provided with network interfaces for

redundancy conÞgurations

The RCU501 provides alarm functions such as:

Fan alarm

Temperature alarm

Voltage alarm

Controls, indicators and system connector

The RCU501 is provided with the NMI and RESET function

controls/buttons located in the upper right-hand corner of the

module.

Figure 2 NMI and RESET buttons layout

2.1.1 NMI push-button

Pressing the NMI function button stops the program execution

momentary.

NMI(Non-Maskable Interrupt) is also generated when watchdog

state is “watchdog_off”.

2.1.2 RESET push-button

Pressing the RESET function button restarts the program

execution and all parameter values are reset to initial values.

Reset will also be generated at power on and by software

generated reset.

2.1.3 RCU condition monitoring

2.1.3.1 Fan and over-temperature status

Two internal alarm signals are monitored by the module:

Fan-not-running alarm

High temperature alarm

2.1.4 Address switches (MAC 1. MAC 2.

MAC 3)

The RCU501 has three hexadecimal switches MAC 1 (S7),

MAC2(S6), MAC 3 (S5) by which you can set the MAC

address for NET A and NET B

MACaddress format for NET A is: 02:41:4C:42:1X:XX

MACaddress format for NET B is: 02:41:4C:42:2X:XX

where X:XX is MAC 1:MAC 2 MAC 3.

2.1.4.1 Example of address setting

The hexadecimal switch settings:

MAC1=1.MAC2=2.MAC3=3

give the MAC addresses:

NET A: 02:41:4C:42:11:23

NET B: 02:41:4C:42:21:23.

2.1.5 MODE switch

The RCU501 has a hexadecimal MODE switch (S4) (see Figure

3 on page 10), which is used to set operational mode. It is used

for ßashing resident application programs to the ßash memory

and for advanced servicing and debugging purposes.

Note

The switch has to be set to 0 (zero) for normal operation (default

setting).

2.1.6 LED indicators

2.1.6.1 Run/Error LED

The Run/Error LED is located on the front cover. It can be red or

green