CJ1-H/CJ1M CPU Unit Ver. 2.0 Upgrades
The following table shows the functional upgrades for CJ1-H/CJ1M CPU Unit
Ver. 2.0.
Functional Upgrades for CJ1-H/CJ1M CPU Unit Ver. 2.0
Function
Downloading and Uploading Individual Tasks
Improved Read Protection Using Passwords
Write Protection from FINS Commands Sent to CPU Units via Networks
Online Network Connections without I/O Tables
Communications through a Maximum of 8 Network Levels
Downloading and Uploading Individual Tasks
Previous CPU Units (Pre-Ver. 2.0 CPU Units)
With the Pre-Ver. 2.0 CPU Units, individual program tasks could not be down
loaded from the CX-Programmer. It was only possible to download the entire
user program.
For example, if several programmers were developing the program, the
project manager had to unify each program after debugging and then down
load the entire user program. Furthermore, the entire user program had to be
downloaded even if just a few changes were made.
Note It was possible to upload individual program tasks with CS/CJ-series PLCs
When several programmers are developing a program, it isn’t necessary for a
project manager to unify the data because just the debugged tasks can be
downloaded/uploaded. Also, transferring individual tasks can help avoid mis
takes

CP1E-NA20DT1-D
Restrictions to Function
Block Use
When several programmers are developing a program, it isn’t necessary for a
project manager to unify the data because just the debugged tasks can be
downloaded/uploaded. Also, transferring individual tasks can help avoid mis
takes.
Developer A
CX-Programmer
Developer B
CX-Programmer
Developer C
CX-Programmer
Edited
Just the edited tasks can be downloaded.
Unchanged
Unchanged
Upload individual tasks.
CS/CJ-series
CPU Unit Ver.2.0 or later
Individual tasks cannot be downloaded for programs containing function
blocks (unit version 3.0 or later only) (uploading is possible).
1-6-2 Improved Read Protection Using Passwords
Read Protection for Individual Tasks Using Passwords
Previous CPU Units (Pre
Ver. 2.0 CPU Units)
CPU Unit Ver. 2.0 or Later
and CX-Programmer
Ver. 4.0 or Higher
| 5453-759 Woodward TMR POWER SUPPLY CHASSIS |
| 3HAC030826-001 ABB Motor incl pinion |
| 3HAC17484-10 Rotational ac motor M8 ABB |
| MFC300-SYKL KROHNE MFC 300 Mass Flow Converter |
| 3HAC030829-001 ABB Motor incl pinion |
| PR6424/014-130 Eddy Current Signal Converter EPRO |
| EASYGEN-3200XT 8440-2082 Woodward EasyGen 3000 series model |
| REF615E-1G ABB Feeder protection and control |
| MVME162P-344SE Motorola Embedded Controller |
| REF615 HBFKBCADNBA1BNN1XG Feeder protection and control ABB |
| REF615 HBFJAEAGABC2BAA11G Feeder protection and control ABB |
| PR6423/015-111 16mm Sensor EPRO |
| PXI-6255 NI PXI Multifunction I/O Module |
| REU610CVVHCNP01 ABB Voltage relay REU610 |
| MXA81A-100-503-00 SEW motion axis multi-axis servo inverter |
With the pre-Ver. 2.0 CS/CJ-series CPU Units, it was possible to read-protect
the entire PLC with a password (referred to as “UM read protection” below),
but it was not possible to protect individual tasks.
UM read protection prevented anyone from displaying, editing, or uploading
the entire user program from CX-Programmer without inputting the correct
password.
Overview
With the CPU Unit Ver. 2.0 or later CPU Units, it is possible to read-protect
individual program tasks (referred to as “task read protection” below) or the
entire PLC. same password controls access to all of the read-protected tasks.
Task read protection prevents anyone from displaying, editing, or uploading
the read-protected set of tasks from CX-Programmer without inputting the cor
rect password. In this case, the entire program can be uploaded, but the read
protected tasks cannot be displayed or edited without inputting the correct
password. Tasks that are not read-protected can be displayed, edited, or mod
ified with online editing.