OMRON

OMRON SYSMAC SCY-P1 Sequential Controller

OMRON SYSMAC SCY-P1 Sequential Controller

Specifications

Ratings

*1.There are no optional functions for the E5CC-U. Refer to Model Number Legend and List of Models on page21.

*2.This function is not supported by the E5CC-B. Refer to Model Number Legend on page20.

*3.With the E5CC-B, there can be up to four set points if event inputs are used to select them.

Power supply voltage A in model number: 100 to 240 VAC, 50/60 Hz

D in model number: 24 VAC, 50/60 Hz; 24 VDC

Operating voltage range 85% to 110% of rated supply voltage

Power consumption

Models with option selection of 000:5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or

1.6 W max. at 24 VDC

All other models: 6.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC

Sensor input

Temperature input

Thermocouple: K, J, T, E, L, U, N, R, S, B, C/W, or PL II

Platinum resistance thermometer: Pt100 or JPt100

Infrared temperature sensor (ES1B): 10 to 70°C, 60 to 120°C, 115 to 165°C, or 140 to 260°C

Analog input

Current input: 4 to 20 mA or 0 to 20 mA

Voltage input: 1 to 5 V, 0 to 5 V, 0 to 10 V,or 0 to 50 mV (The 0 to 50 mV range applies to the

E5CC-U only for those manufactured in May 2014 or later.)

Input impedance Current input: 150 Ω max., Voltage input: 1 MΩ min.

(Use a 1:1 connection when connecting the ES2-HB-N/THB-N.)

Control method ON/OFF control or 2-PID control (with auto-tuning)

Control

output

Relay output

E5CC/E5CC-B:SPST-NO, 250 VAC, 3 A (resistive load), electrical life: 100.000 operations,

minimum applicable load: 5 V, 10 mA (reference value)

E5CC-U: SPDT, 250 VAC, 3 A (resistive load), electrical life: 100.000 operations,

minimum applicable load: 5 V, 10 mA (reference value)

Voltage output

(for driving SSR) Output voltage: 12 VDC ±20% (PNP), max. load current: 21 mA, with short-circuit protection circuit

Linear current output 4 to 20 mA DC/0 to 20 mA DC, load: 500 Ω max., resolution: approx. 10.000

Auxiliary

output

Number of outputs

E5CC: 3

E5CC-B: 2

E5CC-U: 1 or 2 (depends on model)

Output specifications

SPST-NO relay outputs, 250 VAC, Models with 1 output: 3 A (resistive load), E5CC-U models with 2

outputs: 3 A (resistive load), E5CC-B models with 2 outputs: 2 A (resistive load), Models with 3

outputs: 2 A (resistive load), Electrical life: 100.000 operations, Minimum applicable load: 10 mA at

5V (reference value)

Event

IS200AEPAH1AFD GE   GER-4193A GE Power Systems Manual
IS200AEPAH1BKE GE printed circuit board
DS200ADCIH1A GE Genius Adapter Board
FC-IO-0001 Safety Manager System Module   HONEYWELL
330980-71-CN Bently Nevada NSv Proximitor   Sensor
330105-02-12-10-02-CN 3300 XL 11 mm Probe   Bently Nevada
330910-05-15-10-02-00 3300 XL 11 mm Probe   Bently Nevada
PR6423/011-110+CON021 vibration pickup   EPRO
2711P-T10C4D2 Allen-Bradley PanelView   Plus 1000 Operator Terminal
2711P-RP2X Allen-Bradley DC-powered logic   module
2711P-T7C4D2 Allen Bradley PanelView Plus   700 Operator Terminal
SC2L-95UVS2-1CEX FIREYE flame scanners   are micro-processor
95UVS1E-1CEX FIREYE flame scanners are   micro-processor
XV-230-57MPN-1-10 Touch panel EATON
XVS-440-10MPI-1-10 Touch panel EATON
XV-102-B2-35TQR-10 Touch panel EATON
2198-H003-ERS Allen-Bradley Kinetix 5500   Servo Drive
VPL-B0753F-PJ14AA Allen-Bradley VPL   Series Low Inertia servo motors
VPL-B1003T-PJ12AA Allen-Bradley Brushless   AC asynchronous motor

input *1

Number of inputs E5CC: 2 or 4 (depends on model)

E5CC-B: 2 (depends on model)

External contact input

specifications

Contact input: ON: 1 kΩ max., OFF: 100 kΩ min.

Non-contact input: ON: Residual voltage: 1.5 V max., OFF: Leakage current: 0.1 mA max.

Current flow: Approx. 7 mA per contact

Transfer

output *1

Number of outputs 1 (only on models with a transfer output)

Output specifications Current output: 4 to 20 mA DC, load: 500 Ω max., resolution: approx. 10.000

Linear voltage output: 1 to 5 VDC, load: 1 kΩ min., resolution: Approx. 10.000

Setting method Digital setting using front panel keys

Remote SP input *1 *2 Current input: 4 to 20 mA DC or 0 to 20 mA DC (input impedance: 150 Ω max.)

Voltage input: 1 to 5 V, 0 to 5 V, or 0 to 10 V (input impedance: 1 MΩ min.)

Indication method 11-segment digital display and individual indicators

Character height: PV: 15.2 mm, SV: 7.1 mm

Multi SP *3 Up to eight set points (SP0 to SP7) can be saved and selected using the event inputs, key operations,

or serial communications.

Bank switching None

Other functions

Manual output, heating/cooling control, loop burnout alarm, SP ramp, other alarm functions, heater

burnout (HB) alarm (including SSR failure (HS) alarm), 40% AT, 100% AT, MV limiter, input digital

filter, self tuning, robust tuning, PV input shift, run/stop, protection functions, extraction of square root,

MV change rate limit, logic operations, temperature status display, simple programming, moving

average of input value, and display brightness setting

Ambient operating temperature −10 to 55°C (with no condensation or icing), For 3-year warranty: −10 to 50°C with standard mounting

(with no condensation or icing)

Ambient operating humidity 25% to 85%

Storage temperature-25 to 65°C (with no condensation or icing)

Altitude 2.000 m max.

Recommended fuse T2A, 250 VAC, time-lag, low-breaking capacity

Installation environment Overvoltage category II, Pollution Degree 2 (EN/IEC/UL 61010-1