B&R

B&R  DI426  digital input module

B&R  DI426  digital input module

Material number:

2DI426.6

Description:

2010 digital input module 32 inputs 24 VDC, 1 msec, sink/source 8 electrically isolated input groups Order terminal block 1 x TB140 separately!

There is a combined I/O and system bus on every B&R 2005 backplane. Therefore, system and

I/O modules can be inserted on the main backplane. The backplane where the CPU is installed

is the main backplane.

This has the following advantage:

• Only one backplane type is required for main and expansion backplanes (eases stock

management)

Differences to B&R 2010:

• Slower access of I/O data (only applies to the main backplane)

• Limited number of module slots per backplane

• More space in the switching cabinet

The supply voltage for the B&R 2005 control system is provided by a power supply that must be

connected to the far left slot on the backplane

B&R 2005 modules are normally connected using a single row terminal block.

Pin assignments for the individual modules are described in Chapter 3 “B&R 2005 Modules”.

The construction of the terminal block has the following advantages for the PLC user:

• The terminal block can be easily removed using two ejection levers on the module

• The terminal blocks are available with screw clamps and also with cage clamps

B&R 2005 CPUs have the memory for both application programs and the operating system

either integrated in the module or provided on an additional Compact Flash memory card.

The main backplane can hold a maximum of 11 I/O and/or system modules. However, it is still

possible to expand. To do this, the following modules are required:

6.1.1  Expansion Master

The EX350 bus controller is used as an expansion master: The bus controller is a power supply

insert.

6.1.2  Expansion Slave

A power supply module is used as an expansion slave. This power supply module is equipped

with an additional interface, which allows connection of I/O bus expansions. The power supply

must be plugged into the far-left slot of an expansion backplane. A maximum of 4 expansion

backplanes can be connected.

The connection cable between the expansion master and expansion slave is available in two

lengths (1 m or 2 m)

6.2  Remote I/O Bus

The remote I/O allows remote I/O modules (up to 1200 m) to be connected to the CPU. The

following modules are required when implementing a remote I/O system:

6.2.1  Remote Master

The remote master is a system module and must be inserted on the main backplane (combined

system bus and I/O bus). Up to 31 remote slaves can be connected to a remote master.

6.2.2  Remote Slave

The EX250 bus controller is used as remote slave. The bus controller is a power supply insert.

The remote slave communicates via a shielded twisted pair cable with the remote master. A

maximum of 13 I/O modules are operated on each remote slave.

6.2.3  Cabling

In a remote I/O system, remote slaves at distances of up to 1200 m are connected with the

remote master using a shielded twisted pair cable.

IS420ESWAH2A   INDUSTRIAL ETHERNET SWITCH
IS220PTCCH2A THERMOCOUPLE INPUT PACK
IS400TCATH1A Core Analog terminal board   assembly
8440-1936 easYgen-3000 series generator   set controller
H1127-0101 Marine controller
REM543CG212AAAA REM family of power   protection devices
REG670 1MRK002826-AC interval control   device
REC670 1MRK004814-AC intelligent   microcomputer protection device
MDB-8E industrial metal detector control   unit
SYN 5201a-Z,V271 3BHB006714R0271   synchonizing unit
MRU-5 high precision Marine motion sensor
IS230JPDGH1B 28V power distribution   module
GF D563 A101 GFD563A101 3BHE046836R101   exciting device control unit
UFC911B106 3BHE037864R0106 industrial   automation module
GRBTU 3BSE013175R1 ndustrial automation   module
CH-6102 3BHB015648R0001 Transformer   module
UFC921A101 3BHE024855R0101 Control board   module
PPC907BE 3BHE024577R0101 Processor module
SCYC51213 63911607C trigger unit module
SCYC51220 63901075C pulse amplifier   module
LDMUI-01 61320946C interface module
LDMTR-01 63940135F input/output (I/O)   module
LDSTA-01 63940143B igh-performance   controller module