ALSTOM 20×4373 PCB Thyristor Gate
THE DEFAULT DRIVE
INTRODUCTION
The drive may be operated as a simple frequency control drive using the default configuration of Menu 1. In
this configuration all other menus that give access to the advanced features, including vector control are
“invisible”. To gain access to the other menus P1.31 in Menu 1 must be set to 2.
A drive may also be used in Sinusoidal Front End (SFE) applications for which the default configuration of
Menu 1 is included.
Default I/O Connections and Set-up for the Drive
Control and Reference of the drive can be either from the Drive Data Manager™ (Keypad), or via the I/O
terminal blocks TB1 to TB6 at default (TB4 or TB4A and TB4B).
Refer to the Wiring Diagram in the appropriate MV3000e Getting Started or MVDELTA Manual (see Section
1.6). The default drive configuration defined in Menu 1 requires the following I/O connections to be made:
Digital Input Functions.
Analogue Input Functions.
Digital Output Functions.
Analogue Output Functions and Modes.
Each of these connection requirements is now described for all operating modes.
The “default” values listed for “J” drives (AEM Machine Bridge or SFE Mains Bridge) are AFTER the mode
of operation has been selected. The operation mode is selected by P99.01 (see Section 6.57.2).
Digital Input Functions
The Digital Input Function connections to be made for the different operating modes are described in Table
| GE | RV33-1 |
| GE | S710D-EST2 |
| GE | S739DVT |
| GE | SBI-PDP-32 |
| GE | SD-108542 |
| GE | SD-98762 |
| GE | SLN042 IC086SLN042-A |
| GE | SLN080 IC086SLN080-A |
| GE | SM128V |
| GE | SR465-P5-HI-A20 |
| GE | SR469-P5-H-A20-T |
Termination
and Function
Standard
AC Fed Drives
AEM
Machine Bridge
DIGIN 1
SFE
Mains Bridge
DIGIN 2
Remote STOP (+24 V to allow RUN)
Remote RUN
DIGIN 3
Direction (+24 V = Reverse)
DIGIN 4
RUN PERMIT
Control and Reference source (0 V for Keypad, 24 V for Remote)
DIGIN 5
Analogue Reference Select
(0 V = Ref1; +24 V = Ref2) –
DIGIN 6
INTERLOCK
Trip Reset (+24 V = Reset)
Hardware drive inhibit (non programmable function).
(Must be connected to +24 V to run the drive)