GE

GE MVAJ103  10-contact manual reset trip control relay

MVAJ103  10-contact manual reset trip control relay

MVAJ 05x/10x/20x Trip Relays

The MVAJ range consists of highly reliable hinged armature relays designed to directly operate circuit breaker trip coils.

Built to very high specifications, the MVAJ range provides an extremely flexible and reliable link between the protective relays and the circuit breakers.

Numerous features and configurations for multiple tripping schemes

Equipped with a wide range of features and configurations, the MVAJ range can be applied to all types of tripping schemes.

Operating at high speed with very little contact bounce, this range is available in hand, electrical and self-reset models.

Note: Self-resetting devices type MVAJ051 and MVAJ101 have not been designed for use in applications where normally they may be energised (operated/picked-up) continuously.  Accordingly, they should not be used in applications that would require continual energisation.

An external link connection enables selection of high or low burdens and a delayed cut-off is available for high-burden applications.

The MVAJ range is also equipped with AC or DC operating functions for low burden configurations and it ensures immunity to any wiring capacitance discharge.

Auxiliary Relay

Key Benefits

• Compact design

The MVAA is a low burden auxiliary relay for schemes demanding several contacts for

event recording, alarm initiation, contact logic arrangements, etc.

The relay can be supplied fitted with normal duty contacts and/or with heavy duty

blow-out contacts.

MVAA relays are voltage-operated attracted armature units of compact design, featuring

positive action and a high degree of mechanical stability. Voltage is applied to the relay

coils via an internal diode bridge which enables relays to be energised from AC or DC

power supplies.

Typical applications are for general contact multiplication, interlocking and customisation

to suit the substation.

Models

There are five versions of the MVAA relay, each with a different type of contact reset

mechanism:

MVAA 11

Single element relay with self reset contacts (Double element version is

type MVAA 21)

MVAA 13      Single element relay with hand reset contacts (Double element version is

type MVAA 23)

MVAA 14

Single element relay with electrical reset contacts

Contacts

Contacts are made from a silver/copper alloy, shaped and

positioned to ensure very reliable, low resistance operations.

Normal duty make, break and changeover contacts and heavy duty

magnetic blow-out contacts are available in various combinations

(see tables 1. 2 and 3).

Heavy duty magnetic blow-out contacts are recommended for

breaking heavy or highly inductive DC loads. When these are fitted,

the number of contacts available may be reduced (see table 3).

Breaking capacity curves for these contacts are shown in figure 1

on next page.

Operation Indicators

Each relay element is supplied with an optional hand reset

operation indicator.

The indicator consists of a mask, which on operation drops to

expose a broad red strip positioned diagonally on a rectangular

white background.