GE MVAA15 Auxiliary Relay Single Element, Hand + Electrical Reset
Frequency: 50/60 Hz
Withstand rating: The standard relay will withstand 120% of its maximum
Contacts are made from a silver/
voltage rating continuously. High speed variants with time (where tthe
copper alloy, shaped and positioned
10th character of the model number is C or Q) are short time ratedThese
to ensure very reliable, low
must be energised for a maximum of 2 minutes or employ a breakcontact,
resistance operations.
wired externally, to cut off the auxiliary supply after operation
Burdens: 3 W per element at all rated voltages
Normal duty make, break and
Operating times: The operating times are typically 12-25 ms depending on
changeover contacts and heavy
the number of contacts and relay type
duty magnetic blow-out contacts
are available in various combina-
tions (see tables 1.2 and 3).
CONTACT COMBINATIONS
Heavy duty magnetic blow-out
Relay type
Contact combination code letter
Case sizes
contacts are recommended for
(cross reference with detailed
breaking heavy or highly inductive
contact combinations in table 3)
DC loads. When these are fitted, the
MVAA11
number of contacts available may
be reduced (see table 3).
MVAA12
Breaking capacity curves for these
MVAA13*
contacts are shown in figure 1 on
next page.
MVAA14*
OPERATION INDICATORS
MVAA15*
Each relay element is supplied with
an optional hand reset operation
Table 1 Available contact combinations and case sizes for sirgle element relays
indicator.
Relay type
| GE | 44A730240-G01 |
| GE | 44A751101-G01 |
| GE | 469-P1-HI-A20 |
| GE | 469-P1-HI-A20-E |
| GE | 469-P5-HI-A20-E |
| GE | 489-P5-LO-A20 |
| GE | 50510-113-0000 |
| GE | 511-0101-08B |
| GE | 5136-PFB-VME |
| GE | 516TX 336A4940DNP516TX |
| GE | 517-0224-16A-458525 |
| GE | 531X121PCRALG1 |
| GE | 531X301DCCAFG2 |
| GE | 531X303MCPARG1 |
Contact combination code letter
Case sizes
The indicator consists of a mask
(cross reference with detailed
which on operation drops to expose a
broad red strip positioned diagonally
contact combinations in Table 3)
on a rectangular white background
Element 1
Element 2
MVAA21
TECHNICAL DATA
MVAA22
MVAA23*
Voltage
Operating
Table 2 Available contact combinations and case sizes for dual element relays
rating
voltage
(V)
range (V)
24/27
19.2 – 32.4
* Note:
30/34
24.0 – 40.8
When the relays are required to cut off their own supply voltage followingan
48/54
38.4 – 64.8
operation, a special late-acting contact must be used. This contact can be fitted
110/125
88.0 – 150.0
on request and must be wired internally. The number of available coutput
contacts shown in table 3 is reduced by one when a cut-off contacis supplied
220/250
176.0 – 300.0