ALSTOM

ALSTOM PIB903-AR1351 Power Distribution Interface Board

Slide the control board back into the drive and re-connect the

ribbon connectors that were disconnected at step 4.

Secure the control board to the drive chassis using the two screws

and washers removed at step 3. Close the plastic terminal shroud

and secure with the retained screw, then close and secure the

drive doors.

It is wise to strain relieve the CANbus cable before it is connected to the

drive.  Strain relief helps to prevent damage to the CANbus connection or the

cable becoming unexpectedly unplugged.

Electrical noise and electromagnetic interference can be introduced into a

microelectronics system via the cables and wires connected to it.  To avoid

this, wiring which could carry noise, that is ‘dirty’ cables, should be kept away

from cables that are to be kept free from electrical noise or ‘clean’.  Wiring

that falls into the same group can be run together, while wiring from different

groups should be kept apart, though paths may cross at right angles.  All

connections to the CANbus board are considered to be clean.

External Wiring

A CANopen cable is required for connections between drives.  It

should be connected to the ALSPA MV3000e Drive CDC

(Common Drive Controller) at TB7 and TB7B on the CAN 2

module. The position of the terminal block, the method of

routing, restraining and segregating the wiring for the CANopen

connection are shown in the T1676 ALSPA MV3000e Getting

Started Manual.

It is important to strain relieve the CANopen cable before it is

connected to the drive. Strain relief helps to prevent damage to

the CANopen connection and restricts the cable from being

accidentally unplugged.

If the CANopen connections are to be made to an ALSPA

MV DELTA Drive the connection should be made at TB7 on the

ALSPA MVC3002-4001 User I/O Termination Panel. The type of

cable is specified at 4.4.

4.2 Cable Segregation

Electrical noise and electromagnetic interference can be

introduced into a microelectronics system via the cables and

wires connected to it.  Segregation requirements for the wiring

and cables connected to a drive, including those for CANbus,

should be implemented to minimise any possibility of

interference being introduced into the drive system.

Implementation of segregation requirements involves separating

that wiring which could carry electrical noise, referred to as ‘dirty’

wiring, from that which is free from electrical noise, referred to as

‘clean’ wiring.  Wiring that falls into the same group (i.e. ‘dirty’ or

‘clean’) can be run together, while wiring from different groups

should be kept apart, though paths may cross at right angles.

All connections for CANbus are considered to be clean.

The CANbus connection is achieved via the CAN_HI and

CAN_LO and COMMS_GND terminals provided on Terminal

Block TB7/TB7B as detailed at Table 4-1.

The connections at TB7/TB7B are made by screw-type

terminations for each separate flexible cable of the type

All cables should have strain relief to prevent damage to the

CANbus connection at TB7/TB7B.