Alstom 20X1207 Power Board
The following rungs of ladder program will cause a user requested F1 trip if any
configured module should fail. An F1 trip will also be produced if the module type does
not match with the safety values entered in the configuration data.—] [————————————( )–
F372.4 F1.0—] [————————————( )–
F386.4 F1.1
6.1.2
Exchange Mode
The Exchange Mode LS byte contains the communications state indicator in bit 0. This is
set to 1 if the Fieldbus is performing transfers; otherwise it is cleared to 0. The
remainder of the byte is reserved and is cleared to 0.
The Exchange Mode MS byte contains the process data handshake mode as configured
by SyCon.
• Value = 1. Bus synchronous, device controlled.
• Value = 2. Buffered, device controlled.
• Value = 3. Non-consistent, uncontrolled.
• Value = 4. Buffered, host controlled (recommended).
• Value = 5. Bus synchronous, host controlled.
The recommended setting is buffered host controlled. This will have the least impact on
the controller’s scan rate.
All device controlled or uncontrolled settings should be avoided as the Fieldbus
communication will start as soon as power is applied, without waiting for the Ethernet
module (9716-4020) to initialise. The Fieldbus slaves will therefore not be under the
control of the GEM80.
Exchange Counter
This unsigned 32-bit variable contains the count of transfers between the GEM80 and
the Fieldbus module.
Presence Indication
The Fieldbus module maintains a bit array of the active devices detected on the
communications link. It is recommended that the application monitors this bit array and
takes appropriate action on loss of I/O. Word 0 bit 0 represents the master itself and
will always contain 0. Word 0 Bit 1represents the device with address 1 etc.
Presence Words 4 to 7 are not required when using DeviceNET and should be ignored.
Module 1 Module 2 Description
| Honeywell | TC847A1004 |
| ABB | PCD235A PEC80-CIO FU 3BHE032025R0101 |
| ABB | 3ADT218437R0001 D1 UNS4908a V5004 |
| GE | IS2020JPDBG01 |
| GE | IS420UCSBS1A |
| GE | IS215UCVFH2AB |
| ABB | REC670 1MRK004814-AG 1PCS |
| ABB | 3BDH000741R1 CTI 21-P Ex |
| ABB | TPC1582H43A1401E-T 3BHB040969R0001 |
| ABB | PSE105-600-70 |
| GE | IS230PCAAH1B |
| Alstom | MMLG01 |
| METS0 | D201159L |
| GE | DS200TCEAG1BTF |
| METS0 | D201832L |
| GE | IS215AEPAH1C |
| Woodward | easYgen-3200XT-P1 |