Alstom PIB651B Control Board Module

Fixed F-Table

This section contains general guidance for the maintenance of a controller containing

Fieldbus modules.

Each module is allocated 14 fixed F-Tables, used to report errors and statistical

information

Error Code

The Error Code field and the associated pointers are used to identify problems with the

configuration data or failure of the associated Fieldbus module. On power-up these

fields are cleared. On recompilation, syntax checking is performed on the configuration

and problems are reported as follows

System Configuration

Having correctly installed and configured the Fieldbus modules it is then possible to

configure the Fieldbus system using the Hilscher SyCon tool. A detailed description of

the use of this tool is beyond the scope of this manual, although an operation guide is

included in section 7. For full instructions refer to the Hilscher documentation provided

on the CD.

TRICONEX 3009
TRICONEX 3009X
METRIX 5485C-006
HONEYWELL FC-SDO-0824 CC V1.5
Brannstrom BilgMon 488 4A-2936 (15ppm / 220v 60hz)
B&R 3cp340.60-2
B&R 3cp340.60-2
ABB PCD235
Honeywell CC-TAIX51 51307075-175
Honeywell CC-PAIH51 51410069-275
Honeywell CC-TAIX51 51307075-175
Honeywell CC-PAIH51 51410069-275
REGIN E28D-S

This Windows based tool can communicate with the Fieldbus module using a serial link

or over an Ethernet network using TCP/IP. We recommend that you use TCP/IP and the

guide in section 7 follows this route.

The serial link method bypasses the GEM80-500 completely by communicating

directly with the Fieldbus module. This method is suitable for monitoring the network

operation but should not be used for system configuration downloading. As it

communicates directly, new system configurations will be downloaded whether or not

the host GEM80 controller is in a running or halted state.

The TCP/IP method connects directly to the GEM80 TCP/IP Ethernet module.  As a

result the GEM80 Ethernet module is able to examine the commands sent from the

SyCon tool before passing them to the associated Fieldbus module. The running state

of the host GEM80 is also examined by the Ethernet module, attempts to modify

important system parameters will be refused if the host GEM is in the running state.

This results in an error code of 170 at the SyCon tool. The TCP/IP method is also

suitable for monitoring the network operation.

See section 7 for further information on the operation of the SyCon tool.