ALSTOM

ALSTOM MAE00-14 Analog Input/Output Module

Validity Flag (Pn and Pn+12)

The first P-table entry of each module’s configuration data contains a validity flag.  Its

function is to prevent an uninitialised ‘P’-table from being used as configuration

parameters.  The user must insert the hexadecimal value @4801 (module #1) or

@4802 (module #2) into the relevant table entry to signify that the module

configuration data is valid.

The insertion of any other value into the table entry renders inactive the associated

Fieldbus module.

Device Type (Pn+1 to Pn+2 and Pn+17 to Pn+18)

These parameters are used to check that the number of modules fitted and their types

correspond to that expected by the user.  It is recommended to program an F1 trip

should this safety check fail. Refer to section 6.1.1

ABB ACS880 ZCU-14
GE AT868-2-1-1
Honeywell FE-USI-0002
MOOG G771K202A
ABB 07AC91 GJR5252300R0101
Foxboro RH101AB
Foxboro 4000189-530
ABB DHH810-MFT
GE MLJ1005B010F00C
ALSTOM 029.359 325
WOODWARD E8250-502
GE SR489-P5-HI-A20
ABB 3BHL000391P0101
ABB IMASI02
ABB IMASI03
ALSTOM V4559828-0001

Protocol

Board Ref.

Device

Type

(HIGH)

Profibus Master

CIF104P-PB\V

Device

Type

(LOW)

DeciveNet Master

@7910 @9040

CIF104P-DNM\V @7910 @9051

CANopen Master

CIF104P-COM\V @7910 @9050

Profibus Slave

DeciveNet Slave

CANopen Slave

5.2.3 Scan Rate (Pn+3 and Pn+19)

This parameter is used to control the repetition rate of transfers (both input and output)

between the GEM80 tables and the respective Fieldbus module. Scan rates for each

module may be set independently. The value entered represents a rate in milliseconds,

but the rate will limit to 2000 milliseconds. A value of 0 selects free running and a

transfer will occur between each scan of the ladder program.

5.2.4 Input Buffer (Pn+4 to Pn+6 and Pn+20 to Pn+22)

These 3 entries, table letter, offset and quantity together define a buffer for the receipt

of plant data. The table must exist, have write access and have sufficient entries to cater

for the quantity requested. If the buffer does not exist, then the configuration fails.

5.2.5 Output Buffer (Pn+7 to Pn+9 and Pn+23 to Pn+25)

These 3 entries, table letter, offset and quantity together define a buffer for the source

of plant data. The table must exist, have read access and have sufficient entries to cater

for the quantity requested. If the buffer does not exist, then the configuration fails.

5.2.6 Version Buffer (Pn+10 to Pn+12 and Pn+26 to Pn+28)

These 3 entries, table letter, offset and quantity together define a buffer for the receipt

of module version information. If the table letter contains 0. it is assumed that the user

does not wish to read this information, in which case the offset and quantity are

ignored. If the table letter contains any other value, the table must exist, have write

access and have sufficient entries to cater for the quantity requested.

5.2.7 Reserved Parameters

All parameters marked as reserved are for future expansion and must contain the value