Alstom ETU-V3707750 Ethernet Terminal Equipment

Scan Rate (Pn+3 and Pn+19)

This parameter is used to control the repetition rate of transfers (both input and output)

between the GEM80 tables and the respective Fieldbus module. Scan rates for each

module may be set independently. The value entered represents a rate in milliseconds,

but the rate will limit to 2000 milliseconds. A value of 0 selects free running and a

transfer will occur between each scan of the ladder program.

5.2.4 Input Buffer (Pn+4 to Pn+6 and Pn+20 to Pn+22)

These 3 entries, table letter, offset and quantity together define a buffer for the receipt

of plant data. The table must exist, have write access and have sufficient entries to cater

for the quantity requested. If the buffer does not exist, then the configuration fails.

5.2.5 Output Buffer (Pn+7 to Pn+9 and Pn+23 to Pn+25)

These 3 entries, table letter, offset and quantity together define a buffer for the source

of plant data. The table must exist, have read access and have sufficient entries to cater

for the quantity requested. If the buffer does not exist, then the configuration fails.

5.2.6 Version Buffer (Pn+10 to Pn+12 and Pn+26 to Pn+28)

These 3 entries, table letter, offset and quantity together define a buffer for the receipt

of module version information. If the table letter contains 0. it is assumed that the user

does not wish to read this information, in which case the offset and quantity are

ignored. If the table letter contains any other value, the table must exist, have write

access and have sufficient entries to cater for the quantity requested.

5.2.7 Reserved Parameters

ABB RET615E_E HBTCBABAABCBC6BBN1XE
ABB P8451
ABB P8403
ABB SPHSS13
GE DS200ADMAH1AA
GE DS200SNPAH1AB
GE DS3800NHVL
GE DS200FCGDH1ABA
GE UR-9WH
GE XD1-G11
WOODWARD 8440-1935
WOODWARD TG-13
KEBA T155-WL
GE MIB30HICE00000
GE P7650B0C0B6E0A0A
triconex 3723X
triconex 3506X
triconex 3626X
ABB REF615 HBFEAEAGNCA1BNA11G

All parameters marked as reserved are for future expansion and must contain the value

System Configuration

Having correctly installed and configured the Fieldbus modules it is then possible to

configure the Fieldbus system using the Hilscher SyCon tool. A detailed description of

the use of this tool is beyond the scope of this manual, although an operation guide is

included in section 7. For full instructions refer to the Hilscher documentation provided

on the CD.

This Windows based tool can communicate with the Fieldbus module using a serial link

or over an Ethernet network using TCP/IP. We recommend that you use TCP/IP and the

guide in section 7 follows this route.

The serial link method bypasses the GEM80-500 completely by communicating

directly with the Fieldbus module. This method is suitable for monitoring the network

operation but should not be used for system configuration downloading. As it

communicates directly, new system configurations will be downloaded whether or not

the host GEM80 controller is in a running or halted state.

The TCP/IP method connects directly to the GEM80 TCP/IP Ethernet module.  As a

result the GEM80 Ethernet module is able to examine the commands sent from the

SyCon tool before passing them to the associated Fieldbus module. The running state

of the host GEM80 is also examined by the Ethernet module, attempts to modify

important system parameters will be refused if the host GEM is in the running state.

This results in an error code of 170 at the SyCon tool. The TCP/IP method is also

suitable for monitoring the network operation.

See section 7 for further information on the operation of the SyCon tool.