ALSTOM 8933-0000 GEM80 LCD Display Unit
Scan Rate (Pn+3 and Pn+19)
This parameter is used to control the repetition rate of transfers (both input and output)
between the GEM80 tables and the respective Fieldbus module. Scan rates for each
module may be set independently. The value entered represents a rate in milliseconds,
but the rate will limit to 2000 milliseconds. A value of 0 selects free running and a
transfer will occur between each scan of the ladder program.
5.2.4 Input Buffer (Pn+4 to Pn+6 and Pn+20 to Pn+22)
These 3 entries, table letter, offset and quantity together define a buffer for the receipt
of plant data. The table must exist, have write access and have sufficient entries to cater
for the quantity requested. If the buffer does not exist, then the configuration fails.
5.2.5 Output Buffer (Pn+7 to Pn+9 and Pn+23 to Pn+25)
These 3 entries, table letter, offset and quantity together define a buffer for the source
of plant data. The table must exist, have read access and have sufficient entries to cater
for the quantity requested. If the buffer does not exist, then the configuration fails.
5.2.6 Version Buffer (Pn+10 to Pn+12 and Pn+26 to Pn+28)
These 3 entries, table letter, offset and quantity together define a buffer for the receipt
of module version information. If the table letter contains 0. it is assumed that the user
does not wish to read this information, in which case the offset and quantity are
ignored. If the table letter contains any other value, the table must exist, have write
access and have sufficient entries to cater for the quantity requested.
5.2.7 Reserved Parameters
| REOTRON | 567LH-DP24 |
| REXROTH | 0608 801 006 |
| REXROTH | 0608720040 |
| REXROTH | 0608800048 |
| REXROTH | 0608820069 |
| REXROTH | 0608820103 |
| REXROTH | 0608820116 |
| REXROTH | 0608830174 |
| REXROTH | 0608830222 |
| REXROTH | 4WE6Y62/EG24N9K4 R900561276 + HSZ10-26916-AA/G24N9K4M01 R901025684 |
All parameters marked as reserved are for future expansion and must contain the value
System Configuration
Having correctly installed and configured the Fieldbus modules it is then possible to
configure the Fieldbus system using the Hilscher SyCon tool. A detailed description of
the use of this tool is beyond the scope of this manual, although an operation guide is
included in section 7. For full instructions refer to the Hilscher documentation provided
on the CD.
This Windows based tool can communicate with the Fieldbus module using a serial link
or over an Ethernet network using TCP/IP. We recommend that you use TCP/IP and the
guide in section 7 follows this route.
The serial link method bypasses the GEM80-500 completely by communicating
directly with the Fieldbus module. This method is suitable for monitoring the network
operation but should not be used for system configuration downloading. As it
communicates directly, new system configurations will be downloaded whether or not
the host GEM80 controller is in a running or halted state.
The TCP/IP method connects directly to the GEM80 TCP/IP Ethernet module. As a
result the GEM80 Ethernet module is able to examine the commands sent from the
SyCon tool before passing them to the associated Fieldbus module. The running state
of the host GEM80 is also examined by the Ethernet module, attempts to modify
important system parameters will be refused if the host GEM is in the running state.
This results in an error code of 170 at the SyCon tool. The TCP/IP method is also
suitable for monitoring the network operation.
See section 7 for further information on the operation of the SyCon tool.