ALSTOM 9716-4020 Ethernet Communication Board

Module Identification

A rotary switch located on the fieldbus module PCB achieves module identification. A

maximum of two fieldbus modules can be installed into a GEM80-500. each identified

in the system by reserved rotary switch position 2 or 3.

The GEM80-500 Fieldbus driver will find the module with the lowest switch position

and use the configuration parameters from Pn to configure this module, this is referred

to as Module #1.  The next module if fitted will use parameters from Pn+16. this

referred to as Module #2 (see section 5.2).

If a single Fieldbus module is fitted, the rotary switch must be set to position 2 (Module

#1).  If two modules are fitted, one rotary switch must be set to positions 2 (Module

#1) and the other to position 3 (Module #2).

If a module is removed, ensure that the remaining module’s rotary switch is set to

position 2 and that the configuration data starting at Pn are suitable for the application.

N.B. If two modules are fitted, setting the rotary switch to the same position will cause

malfunction of both modules. Selecting any position other than 2 or 3 will cause

malfunction of the host processor.

Introduction

CAUTION

The inclusion and configuration of one or more FIELDBUS modules grants read

and write access to GEM80 data tables. It is the user’s responsibility to ensure

that adequate safeguards are used to prevent dangerous situations arising.

Module Configuration Parameters

An Advanced GEM80 Programmer (or equivalent) must be used to supply the module

configuration parameters.  These parameters must be entered into the P-table of the

host GEM80 Controller by the user before the module can be used.  The GEMLAN-T

Module accesses these parameters on behalf of the Fieldbus module(s) after

completion of its boot procedure.  The GEMLAN-T Module takes approximately one

minute to complete its boot procedure.

If the parameters are subsequently altered, they will be recognised and

validated by the GEMLAN-T Module following a recompilation. During

the validation, Fieldbus communication is halted. If the validation

should fail, the communication remains halted.

Remember that P-table entries above P149 will only exist if specifically

declared in the user program.

For the GEMLAN-T module to access the configuration data successfully, a value must

be written into P74.  This value acts as a pointer to the P-table location containing the

configuration parameters for Fieldbus module #1. Fieldbus module #2 parameters

follow those of module #1 in the P-table.

E.G. if P74 contains a value of 300. the  configuration parameters start at P300.

Inserting a value of 0 into P74 renders inactive all Fieldbus modules of the host

controller.

A detailed description of each configuration parameter is provided in the following

paragraphs.  Table 5-1 provides a reference table.  Table 5-2 is an example of the use

of the P-tables.

RELIANCE ELECTRIC 0-60007-2
RELIANCE ELECTRIC 0-60021-4
RELIANCE ELECTRIC 0-60023-5
RELIANCE ELECTRIC 0-60028-2
RELIANCE ELECTRIC 0-60029-1
RELIANCE ELECTRIC 0-60031-5
RELIANCE ELECTRIC 10VV1/F7252
RELIANCE ELECTRIC 805401-5R
RELIANCE ELECTRIC MD-D4002B
RELIANCE ELECTRIC S-D4006
RELIANCE ELECTRIC S-D4007
RELIANCE ELECTRIC S-D4008
RELIANCE ELECTRIC S-D4012
RELIANCE ELECTRIC S-D4022

发表回复

您的邮箱地址不会被公开。 必填项已用 * 标注