ALSTOM SA46623.B Output Module
ALSTOM SA46623.B Output Module
2.3. Assigning IP address
The IP address is used to identify each controller on the Ethernet network.
Therefore, each controller on the network must have a unique IP address.
2.3.1. The Ethernet board location
To manually assign an IP address to a controller its Ethernet boards dip
switches are used. The location of the Ethernet board differs depending on
product, see figure 2 below.
Ethernet LEDs
12345678
ON
ON
EFFIC Controller
Figure 2. The Ethernet board location
The Ethernet board has four LEDs carrying the following information:
LED Colour LED status Legend
Green
Green
Green
Cont.
Not lit
1 Hz
The module has a link
The module does not sense a link
IP address not set by using the DIP-switch
2 Red 1 H
12345678
ON
z Invalid MAC address (internal error)
2 Red 2H
z Failed to load Ethernet configuration from
FLASH memory
2 Red 4 H
z Internal error
Red
Green
Green
Cont.
Duplicate IP addresses detected
Blinking N/A
Blinking Blinks each time a package is received or
transmitted.
Assigning the IP address to the controller
There are many different ways to assign ip addresses, in this manual the
three most common will be described in the three following sections.
The Ethernet board has a default IP address setting of:
IP address:192.168.0.X
The X in the IP address can be set from 1 to 255 by the configuration switch
on the ethernet board. The switch represents the binary value of the X value
in the IP address.
Example:
The switches are set to
00010100 (20 decimal).
The IP address will be set
to 192.168.0.20
2.3.4. Using configuration switch
ON
12345678
MSB
Make sure that the controller is switched Off.
LSB
Use the configuration switch to assign a unique ip number to the con
troller, a number not used by any other nodes in the network.
Switch On the controller.
Repeat step 1-3 with all the controllers in the network.
Now the IP address of the PC has to be set (the PC that is used for
running the PC MTU software and browsing the web pages).
Note, Assigning IP address to the computer may differ
depending on operating system.
On the PC – click the START button and select Control Panel.
In Control Panel select Network and Dial-up connections and then
Local Area Connection.
Select Properties and highlight Internet Protocol (TCP/IP) and select
Properties.
Click the radio button Specify an IP Address.
10. In the IP address field assign a unique ip number not used by any other
nodes in the network to the PC e.g. 192.168.0.100. The Subnet mask
will normally be automatically filled in (255.255.255.0).
Click OK and close all windows.
11. To complete the setup start the PC-MTU program.
12. From the menu Choose Advanced > Ip config.