FOXBORO

Foxboro P0911QC-C Industrial Control Module

FunctionalSpecifications

FBM218Module • Input:

32groupisolatedchannels

• On-StateVoltage:

15to30VDC

• Off-StateVoltage:

0to5VDC

• Current:

2.2mA(typical)at30VDCInput

• SourceResistanceLimits(AppliestoAllTAs):

◦ On-State:

1kΩ(maximum)at15VDC

◦ Off-State:

100kΩ(minimum)at30VDC

Filter/DebounceTime(1) Configurable(NoFiltering,4.8.16.or32ms)

MaximumPulseCountRate 250Hz

Isolation

(Module/TACombination)

ForTAsthatprovidegroupisolation(RH916CA,RH916XZ,RH916YB,

RH916QA,RH924HA,RH924HP,RH924HQ,RH924HS,andRH924HT),

inputchannelsaregroupisolatedfromground.Fordetails,seeStandard

andCompact200SeriesSubsystemUser’sGuide(B0400FA).These

module/TAcombinationscanwithstand,withoutdamage,apotentialof600

VACappliedforoneminutebetweenthegroupisolatedchannelsand

ground.

HONEYWELL 10310/1/109701
Honeywell 12-HR-43-4
HONEYWELL 1569905-6131140220
HONEYWELL 261A1812P012
HONEYWELL 51120841-101/51120841-201
HONEYWELL 51195066-100 /HF-75632-F
HONEYWELL 51195156-300
HONEYWELL 51196653-100-RP
HONEYWELL 51196655-100 ACX633
HONEYWELL 51202329-606
HONEYWELL 51204126-915
HONEYWELL 51303932-476
HONEYWELL 51304362-300
HONEYWELL 51304487-100
HONEYWELL 51304511-200

PowerRequirements • InputVoltageRange:

24VDC+5%,-10%

• Consumption:

3W(maximum)at24VDC

• HeatDissipation:

5W(maximum)at24VDC(includingcontributionfromfieldpower

supply)

CalibrationRequirements Calibrationofthemoduleandterminationassemblyisnotrequired

RegulatoryCompliance:

ElectromagneticCompatibility

(EMC)

• EuropeanEMCDirective2004/108/EC(PriortoApril20.2016)and

2014/30/EU(BeginningApril20.2016):

Meets:EN61326-1:2013ClassAEmissionsandIndustrial Immunity

Levels

RegulatoryCompliance:Product

Safety • UnderwritersLaboratories(UL)forU.S.andCanada:

UL/UL-ClistedassuitableforuseinUL/UL-ClistedClassI,GroupsA

D;Division2;temperaturecodeT4enclosurebasedsystemswhen

connectedtospecifiedFoxboroDCSprocessormodules.

CommunicationscircuitsalsomeettherequirementsforClass2as

definedinArticle725oftheNationalElectricalCode(NFPANo.70)and

Section16oftheCanadianElectricalCode(CSAC22.1).Formore

information,seeStandardandCompact200SeriesSubsystemUser’s

Guide(B0400FA).

• EuropeanLowVoltageDirective2006/95/EC(PriortoApril20.2016)

and2014/35/EU(BeginningApril20.2016)andExplosive

Atmospheres(ATEX)directive94/9/EC(PriortoApril20.2016)and

2014/34/EU(BeginningApril20.2016):

DEMKOcertifiedasExnAIICT4foruseincertifiedZone2enclosure

whenconnectedtospecifiedprocessormodulesasdescribedinthe

StandardandCompact200SeriesSubsystemUser’sGuide

(B0400FA).ForuseinanenclosuresuitedforanATEXZone2

classifiedarea.

RoHSCompliance ComplieswithEuropeanRoHSDirective2011/65/EU, includingamending

Directives2015/863and2017/2102

IECExCertification IECExCertified

(1)Digitalfilteringavailablefor200SeriesFBMorcompetitivemigrationmoduleswithversion1.25Horlater

firmware