Foxboro P0912CM Dual Coax Cable
Redundant Modules in Foxboro DCS HMI
The redundant pair of modules appear as two independent modules to system
management software applications, such as Foxboro DCS System Manager and
System Manager/Display Handler (SMDH). The functional redundancy for these
modules is provided by their associated control blocks.
Sequence of Events
The Sequence of Events (SOE) software package (for use with I/A Series® v8.x
software and Control Core Services v9.0 or later) is used for acquisition, storage,
display, and reporting of events associated with digital input points in a control system.
SOE, using the optional GPS based time synchronization capability, supports data
acquisition across control processors at intervals of up to one millisecond, depending
on the signal source.
Refer to Sequence of Events (PSS 31S-2SOE) to learn more about this package, and
to Time Synchronization Equipment (PSS 41H-4C2), for a description of the optional
time synchronization capability.
Foxboro DCS with software earlier than V8.x can support SOE through ECB6 and
EVENTblocks. However, these systems do not support GPS time synchronization
and use a timestamp sent by the Control Processor which is accurate to the nearest
second and does not provide synchronization between different Control Processors.
Fieldbus Communication
AFieldbus Communications Module or a Control Processor interfaces to the 2 Mbps
module Fieldbus used by the FBMs. The FBM217 accepts communication from either
path (A or B) of the 2 Mbps Fieldbus. If one path is unsuccessful or is switched at the
system level, the module continues communication over the active path.
Modular Baseplate Mounting
The module mounts on a DIN rail mounted baseplate, which accommodates up to four
or eight Fieldbus Modules. The Modular baseplate is either DIN rail mounted or rack
mounted, and includes signal connectors for redundant Fieldbus, redundant
independent DC power, and termination cables.
Redundant modules must be located in odd and even adjacent positions on the
baseplate (positions 1 and 2. 3 and 4. 5 and 6. or 7 and 8). To achieve the
redundancy, a redundant adapter module is placed on the two adjacent baseplate
termination cable connectors to provide a single termination cable connection. A
single termination cable connects from the redundant adapter to the associated TA.
To system configurator applications and monitoring through SMON, System Manager,
and SMDH,redundant modules appear to be separate, nonredundant modules. The
functional redundancy for these modules is provided by their associated control
blocks
| HITACHI | MPD310A |
| HITACHI | PS6000 |
| HITACHI | PS6515 |
| HITACHI | PS6524 |
| HITACHI | PS6548 |
| HITACHI | TD000A |
| HMS | AB7006 |
| HOKEYWELL | FF-SR05936G |
| HOLOTRAK | IS8500 232/422 |
| HOMATIC | PE1937/23BU |
| HOMER | UEM5-100 |
| HOMEYWELL | LG1093AC01 |
| HONEWELL | CC-TAIM01 |
| HONEWELL | CC-TAIN11 |
| HONEWELL | CC-TAIX11 |