Triconex 3601E/T 115Vac Digital Output
Table 97
Specifications for Term Panel 9671–810
Feature
Description
Panel type
Commoned interposing relay
Points
16
Relay type
Compact, general-purpose power relays with hold-down clamps
Relay contact rating
10A @ 30 VDC or 277 VAC
Relay switching power
(see CAUTION below)
AC: 2500 VA
DC: 90 W
Relay maximum output
cycle rate
Once per scan
Relay expected life at
maximum rated load
100.000 operations
Relay isolation
1000 VAC minimum
1500 VDC minimum
Power consumption per
relay
Less than 2 watts
Products Description
Manufacturer : Triconex
Product No. : 3601E/T
Product type : Digital Output Module
Type : TMR
Output current range : 4-20 mA Input (+6% overrange)
Number of output points : 8
Isolated points : No, commoned return, DC coupled
Resolution : 12 bits
Output Accuracy : <0.25% (in range of 4-20 mA) of FSR (0-21.2 mA), from 32° to 140° F (0° to 60° C)
Over-range protection : +42.5 VDC, continuous
Switch time on leg failure : < 10 ms, typical
Color code : Pea Green
Weight : 4 kg
Dimension : 9 kg
Shipping weight : 5.6 kg
The Triconex Tricon Safety Instrumented System is designed to meet the needs of safety and critical
control applications in oil and gas, power, refining, chemicals, pharmaceutical and biotech industries.
It is based on industry leading TMR technology, is easy to operate and maintain and provides the lowest total cost of ownership.
Models 3502E, 3503E, and 3505E can self-test to detect stuck-On conditions where the circuitry
cannot tell whether a point has gone to the Off state.
Since most safety systems are set up with a deenergize-to-trip capability, the ability to detect Off points is an important feature.
To test for stuck-On inputs, a switch within the input circuitry is closed to allow a zero input (Off) to be read by the optical isolation circuitry.
The last data reading is frozen in the I/O communication processor while the test is running.
EcoStruxure™ Triconex® – Tricon CX
EcoStruxure™ Triconex Safety System – superior protection for people, production and profits
We understand that you need more from your safety instrumented systems than just keeping your operations safe
you need to keep operations running continuously, avoiding any unexpected downtime or interruption that impacts profitability.
EcoStruxure Triconex – Tricon CX is the most powerful safety system from Triconex.
Leveraging the pedigree of the field-proven Tricon, Trident and Tri-GP systems,
Tricon CX is the best possible choice when safety and profitability are critical success factors.