Triconex

Triconex 3604E 24Vdc Digital Output

Compatible Modules

This table describes digital output modules compatible with 9663–610.

Table 72

Modules Compatible with 9663–610

Module Part

Number

Points per

Module

Module Description

Primary

Fuse

3601E

16

115 VAC, non-commoned, opto-isolated, TMR

3A, fast

3601T

16

115 VAC, non-commoned, opto-isolated, TMR

3A, fast

Field Wiring Diagrams

This figure illustrates how to connect the 16-point AC digital output module 3601E or 3601T and

a 9663–610 to the field (1 of 16 points shown)

Simplified Schematics

This is a simplified schematic of a typical 16-point non-commoned AC digital output module

with a commoned digital output panel (1 of 16 points shown).

• Main Chassis—houses Main Processors, memory back-up batteries, communication modules and I/O modules.

• Expansion Chassis—for additional I/O modules up to 100 feet (30meters) away from the Main Chassis. In restricted applications,

operation up to 1.000 feet (300 meters) is supported.

• RXM Chassis—for I/O modules up to 7.5 miles (12 kilometers) away from the Main Chassis.

• Mechanical Keying—Each slot in the Tricon is mechanically keyed to correspond with a specific type of module.

This prevents the installation of modules into improper slots.

Power Supply Modules

• Provide logic power to modules in the Main, Expansion or RXM

Chassis. Available in 24 VDC, 115 VAC and 230 VAC versions. The

power rating of each power supply is 175 watts at 140 ° F (60° C).

Main Processors

The Main Processors execute the system diagnostics and the user-written control program.

Communication Modules

• Tricon Communication Modules (TCM) support a number of Triconex protocols and applications and user-written applications

on Ethernet (802.3) networks, including TriStation, Modbus TCP and OPC.

It also supports RS-232 and RS-485 serial communication with Modbus devices, TriStation 1131. and GPS for time synchronization.

• Enhanced Intelligent

Communication Modules (EICM) support RS-232. RS-422 and RS-485 serial communication with Modbus devices and TriStation 1131.

• Network Communication Modules (NCM) support a number of Triconex protocols and applications and

user-written applications on Ethernet (802.3) networks, including TriStation 1131.

• Safety Manager Modules (SMM) act as an interface between a Tricon controller and a Honeywell Universal Control Network (UCN),

one of three principal networks of the TDC-3000 DCS.

• Hiway Interface Modules (HIM) act as an interface between a Tricon controller and a

Honeywell TDC-3000 Hiway Gateway and Local Control Network (LCN).

• Advanced Communication Modules (ACM) allow a Tricon controller to interface with

a Foxboro Industria Automation (I/A) Series DCS and TriStation 1131.