TRICONEX MA2211-100S2 – Communication Module
TRICONEX MA2211-100S2 – Communication Module, Redundant, High-Speed
The TRICONEX MA2211-100S2 is a cutting-edge automation product designed for a wide range of industries,
including the power, petrochemical, and general automation sectors.
This model stands out for its exceptional input/output capacity, durability, and performance indicators, making it a reliable and efficient choice for various applications.
Key technical features of the MA2211-100S2 include a high input/output capacity, allowing for seamless integration with complex systems.
Its durable construction ensures long-term reliability, even in harsh industrial environments.
Performance indicators such as response time and accuracy are top-notch, guaranteeing precise control and monitoring capabilities.
In power industry applications, the MA2211-100S2 excels in power grid automation, offering real-time monitoring and control of critical systems.
In petrochemical settings, such as refinery process control, this model provides precise regulation of chemical processes, enhancing safety and efficiency.
In general automation tasks like assembly line optimization, the MA2211-100S2 streamlines production processes, reducing downtime and maximizing output.
Field Wiring Diagrams
This figure illustrates how to connect a 32-point digital input module and a 9561–810 with a DC
power supply to the field
This figure illustrates how to connect a 32-point digital input module and a 9561-810 with an AC
power supply to the field
Simplified Schematics
This is a simplified schematic of a typical 32-point commoned digital input module with a
commoned digital input panel (1 of 32 module points shown)
9562-810 (48 V, commoned, 16 pts.)
Termination panel 9562–810 is compatible with 48 volt digital input modules and has 16 input
points and commoned power terminals (PWR+ and PWR–). Each input point is protected by a
fuse with a blown-fuse indicator.
The modules compatible with 9562–810 have 32 points, which means you must use two term
panels for each digital input module.
Each term panel comes with two sets of labels: 1-16 and 17-32. For information on how to apply
the labels, see Appendix F, Panel Labels.
Specifications
This table describes specifications for 9562–810.
Table 22
Specifications for Term Panel 9562–810
Feature
Description
Panel type
Commoned
Points
16
Leakage current per point
Maximum: 3.5 mA
Typical: 2.0 mA