TRICONEX 2101 – Main Processor Module, Modular, High-Performance
Pulse Totalizer Input Modules
This table identifies termination products you can use with pulse totalizer input modules.
Note You need two termination panels for each 32-point pulse totalizer input module.
Digital Output Modules
This table identifies termination products you can use with 16-point non-supervised digital
output modules.
Note You need one termination panel (or cable) for each 16-point non-supervised DO module.
Table 5 Termination Products for 32-Point Pulse Totalizer Input Modules
Termination Option 0–1 kHz (3515)
Basic termination panel 9753-110
Nonincendive termination panel 9572-610
Fanned-out cable Contact Triconex for availability of pulse totalizer fanned-out
cables.
Table 6 Termination Products for 16-Point Non-Supervised Digital Output Modules
Termination
Option
115 VAC
(3601E)
115 VAC
(3601T)
120 VDC
(3603B)
120 VDC
(3603E)
120 VDC
(3603T)
24 VDC
(3604E)
48 VDC
(3607E)
Standard
termination panel,
commoned
9661-610
9663-610
9663-610 n/a 9661-910
9664-810
9664-810 9662-810 9667-810
Standard
termination panel,
non-commoned
9661-110
9664-110
9664-110 n/a n/a n/a 9662-110 9667-110
Basic termination
panel
9651-110 n/a n/a 9651-110 9651-110 9653-610 9652-610
Nonincendive
termination panel
n/a n/a n/a n/a n/a 9671-610 n/a
Relay panel,
commoned
9670-610 n/a n/a 9673-810 9673-810 9671-810 9672-810
Relay panel,
non-commoned
9670-110 n/a n/a n/a n/a n/a n/a
Special panel,
non-commoned
n/a n/a 9251-210 n/a n/a n/a n/a
Fanned-out cable 9101-010 n/a n/a 9101-010 n/a 9101-010 9101-010
Supervised Digital Output Modules
This table identifies termination products you can use with 8-point supervised digital output
modules. You can use only one of the terminations listed in a particular module’s column.
Table 7
Termination Products for 8-Point Supervised Digital Output Modules
Termination Option
115 VAC
(3611E)
120 VDC
(3613E)
24 VDC
(3614E)
24 VDC (low power)
(3615E)
48 VDC
(3617E)
Standard termination
panel, commoned
9661-510
9661-810
9662-910
9662-710
9667-910
Note You need one termination panel (or cable) for each 8-point or 16-point supervised DO
module.
Table 8
Termination Products for 16-Point Supervised Digital Output Modules
Termination Option
120 VDC (3623)
120 VDC (3623T)
24 VDC (3624)
Standard termination panel,
commoned
9661-910
9664-810
9662-610
Basic termination panel
9651-110
9651-110
9653-610
Nonincendive termination panel n/a
n/a
9671-610
Fanned-out cable
9101-010
n/a
9101-010
Supervised/Non-Supervised Digital Output Modules
This table identifies termination products you can use with 32-point supervised/non
supervised digital output modules.
Table 9
Termination Products for 32-Point Supervised/Non-Supervised Digital Output
Modules
Termination Option
24 VDC (3625)
Standard termination panel, commoned
9662-610
Basic termination panel
9653-610
Nonincendive termination panel
9671-610
Fanned-out cable
9101-010