Communication Module Triconex CM3201
Each TCM supports an aggregated data rate of 460.8 Kb/s for all four serial ports.
Tricon programs use variable names as identifiers, while Modbus devices use numeric
addresses called aliases.
Therefore, each Tricon variable name must be assigned an alias that will be read by
or written to the Modbus device.
An alias is a five-digit number that represents the Modbus message type and the address
of the variable in the Ticon. An alias number is assigned in the TriStation.
Any standard Modbus device can communicate with Tricon via TCM, provided an alias is
assigned to the Tricon variable.

The alias number must also be used when the host accesses the Tricon through other
communication modules.
Each TCM contains two network ports – NET 1 and NET 2. Models 4351A and 4353 have
two copper Ethernet (802.3) ports and Models 4352A and 4354 have two fiber optic Ethernet ports.
NET 1 and NET 2 support TCP/IP, Modbus TCP/IP Slave/Master, TSAA, TriStation,
The NET 1 also supports the Peer-to-Peer and Peer-to-Peer Time Synchronization protocols.
A single Tricon system supports up to four TCMs, which must reside in two logical slots.
Different TCM models cannot be mixed in a logical slot.
Each Tricon system supports a total of 32 Modbus masters or slaves, including network and serial ports.
The hot standby feature does not apply to TCMs, but you can replace a defective
TCM while the controller is online.
The EcoStruxure Triconex Safety Intelligent Enclosure (SIE) provides
an integrated solution designed to be mounted close to field instrumentation to reduce cabling
The SIE includes Tricon™ CX Universal Input/Output (UIO) modules, power supplies,
and External Termination Panels (ETPs) that are pre-installed and tested,
and can be connected to a wide range of field devices.
The factory-manufactured SIE supports Schneider Electric’s Flexible Lean Execution strategy,
which shortens project schedules and reduces the risk of startup delays.
Note: Images are for illustrative purposes. Your product may look slightly different.
The Safety Intelligent Enclosure (SIE) consists of a
wall-mounted stainless steel cabinet, Tricon CX I/O
Expansion Chassis, Universal Input/Output (UIO)
modules, power supplies, fans, and termination panels
Thermocouple Input Modules
This table identifies termination products you can use with 16-point thermocouple input
modules. You can use only one termination listed in a particular module’s column.
Table 15
Termination Products for 16-Point Thermocouple Input Modules
Termination Option
Type E, J, K, and T; High-Density (3708E)
Standard termination panel
9765-610
Nonincendive termination panel
9786-110
RG 1.180 Term Panel
9782-110
Note You need one termination panel for each 16-point thermocouple input module.
This table identifies termination products you can use with 32-point thermocouple input
modules.
Table 16
Termination Products for 32-Point Thermocouple Input Modules
Termination Option
Type J, K, and T; Differential; Non-Isolated (3706A)
Standard termination panel, upscale
9766-210
Standard termination panel, downscale
9766-510
Nonincendive termination panel, upscale
9784-610
Nonincendive termination panel, downscale 9785-610