DEIF

DEIF iE 650 PLC Extreme robust Programmable Automation controller with EtherCAT based I/O

iE 650 PLC

Extreme robust Programmable Automation controller with EtherCAT based I/O

The iE 650 PLC is our high-end offering for tomorrow’s intelligent energy solutions requiring high reliability in demanding climatic conditions experienced on land, marine or container-based turn-key solutions.

The iE 650 PLC is a PLC-based programmable automation controller (PAC) suitable for land, marine, and wind power control

applications. It is class approved, designed to marine specifications and can withstand very harsh operating conditions.

The controller is a highly flexible, modular PLC and I/O system that is designed for usage across a wide range of industrial

applications. It is reliable, robust and flexible.

EtherCAT is used as native communication protocol both as the backplane communication and as interconnection between

multiple iE 650 PLC racks via electrical or fibre optical connections. Other DEIF EtherCAT I/O modules or third party

EtherCAT I/O modules can also be connected

Software versions

The information in this document relates to software versions:

Software

iE PLC bundle

BSP

CODESYS CONTROL

CODESYS IDE

CODESYS TSP

Details

Signed Software bundle with components:

Board Support Package (Operating System)

CODESYS Control run-time

Version

2.0.17.1

5.0.9.1

3.5.22.10

PC software for development of CODESYS applications

iE x50 CODESYS TSP (Target Support Package)

Environment

Category Specification Standard

Operating temperature -40 to 70 °C

IEC 60068-2-1

IEC 60068-2-2 Storage temperature -40 to 85 °C

Reference temperaure 15 to 30 °C

Altitude Up-to 4000 m without de-rating (for deployment above 4000 m, contact

Product Management).

Climate

All modules are conformal coated, hence protected against moisture, mold,

dust, corrosion and other environmental stresses.

IEC

60068-2-30

test Db 55 °C at 97 % relative humidity, condensing

Dry heat test IEC 60068-2-2

Cold test IEC 60068-2-1

Tests

Category Specification Standard

Performance test and

performance check Criteria/standard: All inputs, outputs and interfaces are functional.

Radiated E-field emission

• 30 to 230 MHz: 50 dB (μV/m) Qp 10 m

• 230 to 1.000 MHz: 57 dB (μV/m) Qp 10 m

• 1 to 3 GHz: 76 dB (μV/m) Q peak 3 m

• 1 to 3 GHz: 56 dB (μV/m) average 3 m

• 3 to 6 GHz: 80 dB (μV/m) Q peak 3 m

• 3 to 6 GHz: 60 dB (μV/m) average 3m

IEC 61000-6-4

IEC 60255-26

Conducted emission  IEC 61000-6-4

IEC 60255-26

Electrical fast transients test

(EFT) Criteria B

Levels extended to:

• DC-power port: ±4 kV

• Functional Earth port: ±4 kV

• Signal input and output ports: ±2 kV

• Communication ports: ±2 kV

• Repetition frequencies: 5 KHz and 100 KHz

• Duration each polarity: 1 min.

EN 61000-4-4

EN 61000-6-2

RF E-Field immunity  Criteria: A 80 to 2.000 MHz: 12 V/m

2 to 3 GHz: 10 V/m

EN 61000-4-3

EN 61000-6-2

Electrostatic discharge

(ESD) Criteria: B Level extended to: Contact 6 kV EN 61000-4-2

EN 61000-6-2

Slow transients test, surge Criteria: B

Levels extended to:

• Digital inputs: ±1 kVp DM and ±2 kVp CM

• Digital outputs: ±1 kVp DM and ±2 kVp CM

• Analogue inputs: ±3 kVp DM and ±3 kVp CM

• Analogue outputs: ±1 kVp DM and ±2 kVp CM

• Temperature inputs: ±3 kVp DM and ±3 kVp CM

• Main power supply: ±3 kVp DM and ±3 kVp CM

• Dig output power supply: ±3 kVp DM and ±3 kVp CM

EN 61000-4-5

EN 61000-6-2