SAUTER Valve actuator ASM 105S/115S series ASM115SF152
SAUTER Valve actuator ASM 105S/115S series ASM115SF152
ASM 124: Damper actuator
How energy efficiency is improved
Torque-dependent cut-off facility for efficient usage of energy
Features
• For operating air dampers, shut-off dampers, butterfly valves and multi-leaf dampers
• For controllers with switching (2- and 3-point) output
• Synchronous motor with electronic activation and cut-out
•Maintenance-free gear unit
• Electronic end position detector and motor cut-off
• Self-centring spindle adapter for fitting onto damper spindle
• Gear unit can be disengaged to position the damper and for manual adjustment
• Suitable for all fitting positions
• Threaded holes (M5) for fitting to bracket
• Version with halogen-free cable on demand
Technical data
Power supply
Power supply 230 V~ ±15%, 50…60 Hz
Power supply 24 V~ ±20%, 50…60 Hz
Parameters
Torque and holding torque 18 Nm
Running time for 90° 120 s
Angle of rotation Max. 95°
Admissible damper shaft Ø 12…20 mm, □ 10…16 mm
Admissible damper shaft (hardness) max. 300 HV
Operating noise < 30 dB (A)
Response time 200 ms
Ambient conditions
Admissible ambient temperature–20…55 °C
Admissible ambient humidity < 95% rh, no condensation
Construction
Weight 1.2 kg
Housing Lower section black, upper section
yellow

ASM115SF152
Housing material Fire-retardant plastic
Power cable 1.2 m long, 3 × 0.75 mm²
Standards and directives
Type of protection IP40 (EN 60529), IP43 (EN 60529),
IP54 (EN 60529), IP55 (EN 60529)
Protection class 230 V II (EN 60730)
Protection class 24 V III (EN 60730)
EMC Directive 2014/30/EU EN 61000-6-1. EN 61000-6-2
EN 61000-6-3. EN 61000-6-4
Low-Voltage Directive 2014/35/EU EN 60730-1. EN 60730-2-14
Over-voltage categories III
Degree of contamination II
Mode of operation Type 1 AB (EN 60730)
Type 1 C (EN 60730)
Software A (EN 60730)
Overview of types
Type Voltage Power consumption
ASM124F120 230 V~ 2.9 W, 5.6 VA
ASM124F122 24 V~ 2.3 W, 2.4 VA
Power consumption when idle:
A ASM124F120: 0.5 W, 5.1 VA
A ASM124F122: 0.03 W, 0.4 VA
Accessories
51.025
Type
0361977001
0370059000
0370990001
0370990002
0370992001
0370992002
0372200001
0372201001
0372202001
0372203001
0372204001
0372455001
Description
Assembly materials for M3R/M4R, MH32F/MH42F with ASM 124
Clamping lever for shaft, Ø 8…18 mm
Auxiliary change-over contacts, single
Auxiliary change-over contacts, double
Potentiometer, 2000 Ω, 1 W
Potentiometer, 130 Ω, 1 W
Fitting bracket
Spindle extension with coupling
Lever, fitting strip
Driver axle for auxiliary contacts
Spindle for clamping lever 0370059
Assembly part; DEF DN25…65 for ASM 124/134
0372455002
Assembly part; DEF DN80…100 for ASM 124; DN125 for ASM 134
A Auxiliary change-over contacts: Infinitely variable 0…90°, admissible load 5(2) A, 24…230 V
Description of operation
The concept of synchronous motor and electronics enables the parallel operation of multiple air
dampers with different torques. When voltage is applied to the cable, the control unit to be activated is
moved to any desired position.
Direction of rotation for 3-point control (viewing the spindle adaptor from the actuator):
• The spindle adaptor turns in the clockwise direction, with the voltage on the brown cable (2a).
• The spindle adaptor turns in the anti-clockwise direction, with the voltage on the black cable (2b).
Direction of rotation for 2-point 24V control (viewing the spindle adaptor from the actuator):
There is always voltage on the black cable (2b):
• The spindle adaptor turns in the clockwise direction, with the voltage on the brown cable (2a).
• The spindle adaptor turns in the anti-clockwise direction, with no voltage on the brown cable (2a).
Direction of rotation for 2-point 230V control (viewing the spindle adaptor from the actuator):
There is always voltage on the brown cable (2a):
• The spindle adaptor turns in the anti-clockwise direction, with the voltage on the black cable (2b).
• The spindle adaptor turns in the clockwise direction, with no voltage on the black cable (2b).
In the end positions, the electronic end position detection (motor cut-off) is activated. In the case of an
overload, a magnetic coupling secures the gear unit. The effective end position results from the limit
stop of the damper or the angle-of-rotation limit or by reaching the maximum angle of rotation of 95°.
The manual adjustment is performed by turning the spindle adaptor after releasing the gear unit (but
ton on housing cover).
With 3-point control, the direction of rotation is changed by swapping the connections