SAUTER

SAUTER Valve actuator ASM 105S/115S series ASM105SF132

ASM 105S, 115S F132: Damper actuator with SAUTER

Universal Technology (SUT)

How energy efficiency is improved

Torque-dependent cut-off facility for efficient usage of energy

Features

• For controllers with switching (2- and 3-point) or continuous output (0…10 V)

• Self-centring spindle adapter

• Gear unit can be disengaged to position the damper and for manual adjustment

• Stepping motor with electronic activation and cut-out

•Maintenance-free

• Intelligent adaptation of rotation angle, incl. feedback adjustment

• Free configuration using the CASE Drive PC tool

• Suitable for all fitting positions

Technical data

Power supply

Power supply 24 V~ ±20%, 51…60 Hz

Power supply 24 V= ±20%

Parameters

Angle of rotation Max. 95°

Admissible damper shaft Ø 8…16 mm, □ 6.5…12.5 mm

Admissible damper shaft (hardness) Max. 300 HV

Operating noise < 30 dB (A)

Response time 200 ms

Positioner Control signal y 0…10 V, Ri > 100 kΩ

Positional feedback signal y0 0…10 V; load > 10 kΩ

Starting point U0 0 or 10 V

Control span ΔU 10 V

Switching range Xsh 200 mV

Ambient conditions

Admissible ambient temperature–20…55 °C

Admissible ambient humidity < 95% rh, no condensation

Construction

Weight 0.7 kg

Housing Lower section black, upper section

yellow

Housing material Fire-retardant plastic

Power cable 1.2 m long, 5 × 0.5 mm²

Standards and directives

Type of protection IP54 (EN 60529)

Protection class III (IEC 60730)

CE conformity EMC Directive 2014/30/EU EN 61000-6-1

EN 61000-6-3

EN 61000-6-4

Directive 2006/95/EC EN 1050

Overview of types

ASM105SF132

Type Rotational torque and holding

torque (Nm)

Running time for 90° Power consumption

ASM105SF132 5 35/60/120 s 5.0 W, 9.0 VA

ASM115SF132 10 60/120 s 4.8 W, 8.7 VA

Description of operation

Depending on the type of connection (see connection diagram), the actuator can be used as a contin

uous 0…10 V, 2-point (OPEN/CLOSE) or 3-point actuator (OPEN/STOP/CLOSE) with an intermediate

position. The running time of the actuator can be set with switches S1 and S2 according to require

ments.

The manual adjustment is performed by releasing the gear unit using the adjuster beside the connec

tion cable and simultaneously adjusting the spindle adaptor.

Intended use

This product is only suitable for the purpose intended by the manufacturer, as described in the “De

scription of operation” section.

All related product regulations must also be adhered to. Changing or converting the product is not ad

missible.

Additional technical data

The upper section of the housing with the cover, indicator knob and cover knob contains the stepping

motor and the SUT electronics.

The lower section of the housing contains the maintenance-free gear unit, the gear-release lever and

the spindle adaptor.

Auxiliary change-over contacts

Switch rating max. 230 V AC, current min. 20 mA at 20 V

Switch rating max. 4…30 V DC, current min. 1…100 mA

Power consumption

Type

Running time [s]

Status

Active power [W]

ASM 105S F132

Connection as 2-point control unit

This OPEN/CLOSE activation can be performed via 2 cables. The actuator is connected to the volt

age via the blue and brown cables. The damper actuator is moved to the end position by connecting

the voltage to the black cable (clockwise direction to 100% angle of rotation). After the voltage is

switched off, the actuator moves to the opposite end position. The unused red and grey wires must

not be connected or come into contact with other cables. We recommend that you insulate these.

发表回复

您的邮箱地址不会被公开。 必填项已用 * 标注